Panasonic CS-VE9NKE Service Manual page 58

Hide thumbs Also See for CS-VE9NKE:
Table of Contents

Advertisement

Non-stop heating deice operation is prohibited when any of the following condition is met
Protection control that limit capacity.
o
Heat charge temperature sensor abnormal.
o
Heat charge cycle abnormal.
o
Outdoor pipe temperature sensor 2 abnormal.
o
The outdoor temperature range falls under -30°C.
o
Deice stop condition
Outdoor air temperature is more than 9°C
o
13.3.7 Heat Storage 2-Way Valve Control
Quick Heating
Heat storage 2-way valve will open for 30 seconds to speed up heating during Powerful heating start time.
o
Thermo OFF comfortable control
Heat storage 2-way valve will open before thermo OFF to change the room temperature during thermo OFF
o
and to reduce loss during thermo ON.
Start condition
Control content
Heatstorage 2-way valve ON and OFF maximum 3 times consecutively.
58