13.1.8
4-Way Valve Operation Detection Control (Switching Abnormality between
Cooling and Heating)
When indoor heat exchanger exceeds 45°C (Cooling operation) or 0°C (Heating and Deice operation) in
4 minutes or 3 minutes (Deice operation) after compressor start, compressor will stopped.
If above condition occurs 4 times per 30 minutes or 4 times per 40 minutes (non-stop heating deice operation),
timer LED blinks "F11" indicated.
13.2
Protection Control for Cooling and Soft Dry Operation
13.2.1
Outdoor Air Temperature Control
The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the
diagram below.
This control will begin 1 minute after the compressor starts.
Compressor frequency will adjust base on outdoor air temperature.
13.2.2
Cooling Overload Control
Detects the Outdoor pipe temperature and carry out below restriction/limitation (Limit the compressor Operation
frequency).
The compressor stop if outdoor pipe temperature exceeds 61°C.
If the compressor stops 4 times in 20 minutes, Timer LED blinking (F95 indicated: outdoor high pressure rise
protection).
13.2.3
Freeze Prevention Control 1
When indoor heat exchanger temperature is lower than 0°C continuously for 6 minutes, compressor will stop
operating.
Compressor will resume its operation 3 minutes after the indoor heat exchanger is higher than 5°C.
At the same time, indoor fan speed will be higher than during its normal operation.
If indoor heat exchanger temperature is higher than 5°C for 5 minutes, the fan speed will return to its normal
operation.
13.2.4
Freeze Prevention Control 2
Control start conditions
During Cooling operation and soft dry operation
o
During thermo OFF condition, indoor intake temperature is less than 10°C or
Compressor stops for freeze prevention control
Either one of the conditions above occurs 5 times in 60 minutes.
o
Control contents
Operation stops.
o
Timer LED blinks and "H99" indicated.
o
55