13.3.4
Low Temperature Compressor Oil Return Control
In heating operation, if the outdoor temperature falls below -10°C when compressor starts, the compressor
frequency will be regulated up to 600 seconds.
13.3.5
Cold Draught Prevention Control
When indoor pipe temperature is low, cold draught operation starts where indoor fan speed will be reduced.
13.3.6
Deice Operation
When outdoor pipe temperature and outdoor air temperature is low, deice operation starts.
Deice Start condition
Outdoor air temperature sensor1 detects temperature below 9°C continuously for 40 minutes, for the next 20
o
minutes if the temperature is below line A for 3 minutes.
Outdoor air temperature sensor1 detects temperature below 9°C continuously for 40 minutes, if the
o
temperature is below line A and line B for 3 minutes.
Heating operation operates without deicing operation continuously for 24 hour, outdoor temperature is below
o
3°C.
Non-stop Heating Deice Operation
Without Heating Deice Operation
4-way valve is switched and deicing is performed by cooling cycle.
o
Unit stop heating operation for maximum 12 minutes.
o
During this operation the power indicator blinks and the vertical airflow direction louver is left open.