H0 - H3 Error Codes
H0
Decrease frequency due to overload.
Status:
All systems operate normal with decrease in
capacity
H1
Defrosting
Status:
Defrosting will occur in heating mode.
Compressor will operate while indoor fan
stops.
H3
Overload Protection for Compressor
Status:
During cooling mode, compressor will stop,
indoor fan will run. Heating mode all units
stop.
154
Error Code Diagnostics
Fault & Status
Possible Causes
1. Refer to "E8" troubleshooting procedures
Normal function
1. Wiring terminal OVC-COMP is loose. In
normal state the resistance should be less
than 1 ohm,
2. Refer to "E4" troubleshooting procedures.