Troubleshooting; Alarm Issues; Alarm, (False) Fan Fail; Alarm, (False) Low Limit (Freeze Stat) - KMC Controls FlexStat Operation Manual

Bacnet programmable thermostats
Hide thumbs Also See for FlexStat:
Table of Contents

Advertisement

Troubleshooting

Alarm Issues

Alarm, (False) Fan Fail

• Check configuration. Be sure the Fan Status
option is not selected when there is no sensor/
switch for it.
• Check that the IN2 (fan status) input pull-up
resistor switches are fully latched in the correct
positions. Any passive, dry contact should use
the 10K Ohm setting. (See the Connections and
Wiring section of the relevant FlexStat Installa-
tion Guide.)
• Check IN2 (fan status) input wiring.
• Check the connected fan status sensor/switch.
• Using BACstage or TotalControl, check that AI2
(fan status) is not configured as "Out Of Service."

Alarm, (False) Low Limit (Freeze Stat)

Check the Low Limit Alarm setting—see Damper
Setup on page
6.
• Check configuration. Be sure the Economizer
option is not selected when there is no mixed air
temperature sensor.
• Check that the IN3 (mixed air temp.) input
pull-up resistor switches are fully latched in the
correct positions (see the Connections and Wir-
ing section of the relevant FlexStat Installation
Guide).
• Check IN3 (mixed air temperature) input wiring.
• Check the connected mixed air temperature sensor.
• Using BACstage or TotalControl, check that AI3
(mixed air temp.) is not configured as "Out Of
Service."
NOTE: After a low limit alarm is generated, the
fan will not run until after the FlexStat is
restarted. (See Resetting the FlexStat on
page
16.)

Alarm, (False) Space Temp. or Humidity

See Alarms on page
See Temperature Reading Is Incorrect on page
See Temperature Setpoint Is Not Maintained on
page
23.
• Using TotalControl, adjust the limits or time
delay.
FlexStat
13.

Communication Issues

KMD-5576 Communication Issues

• Upgrade to the latest version of BACstage (ver.
2.4.0.25 or later required).
• Check the settings for the USB port on the
computer (Device Manager > Ports) and the
MS/TP port in BACstage (Access > Connection
Parameters).
• Reduce the Max Master number down to the
minimum needed for that network—see (Ad-
vanced) BACnet Communications on page
• Install latest driver and check latency settings.
See Latency Settings for KMD-5576 Service Bul-
letin (SB0308A) on the KMC web site.
See also MS/TP Network Communication
below.

MS/TP Network Communication Issues

• Check MAC address and device instance num-
bers (especially for duplicate numbers on the
network)—see (Advanced) BACnet Communica-
tions on page 8 and (Advanced) BACnet Device
Properties on page
• Check that EOL switches are fully latched in the
correct positions (see the relevant FlexStat Instal-
lation Guide).
Check baud rate—see (Advanced) BACnet Com-
munications on page
• Reduce the Max Master number down to the
minimum needed for that network—see (Ad-
vanced) BACnet Communications on page
See Wiring Issues on page