Restore Factory

Restore Factory (restoring the FlexStat to the factory
settings) does the following:
• Clears present values.
• Restores the object database/configuration to the
defaults.
• Restarts the controller's (factory installed) Con-
trol Basic programs.
NOTE: The MAC address and device instance are
not restored to their original defaults, and
custom Control Basic programs are not
deleted. If custom Control Basic programs are
installed, all factory programs are restarted
but all custom Control Basic programs are
halted. Custom programs may be restarted by
loading/running the programs from the CB
Programs menu. See (Advanced) CB (Control
Basic) Programs on page
CAUTION
When returned to factory defaults, analog out-
puts will go to zero and relays will go to their
normally open state. Before restarting the ther-
mostat, manually override equipment as needed.
FlexStat
7.
17
CAUTION
After a return to factory defaults, applications are
unconfigured. You must select the desired appli-
cation and appropriate settings before connected
equipment will operate properly. (See
Application Options on page
To restore the FlexStat to factory settings:
1. Select Restore Factory from the Advanced > De-
vice menu.
2. When prompted for the required restart, press
Enter. (To Cancel, press the right button and then
Enter or just let the display time-out).
3. After the FlexStat has restarted, review the set-
tings and reconfigure as needed.
ADVANCED
APPLICATION
CB PROGRAMS
INSTANCE: 1
COMMUNICATION
DATE/TIME
NAME: FlexStat_101
DEVICE
LOCATION: KMC Controls
LIMITS
SECURITY
RESTART: NO
RESTORE FACTORY:
(Advanced)
6.)
DEVICE
RESTART REQUIRED!
RESTART
CANCEL
YES