Connecting battery module cables
It is recommended to use four battery modules for power supply, including two positive battery modules and two
negative battery modules, using one-into-multiple battery cables (optional) to connect. The cables of the positive
battery module are shown in Figure 2-25, and the cables of the negative battery module are shown in Figure 2-26.
Connect the Bat+, Bat-N, Bat- and PE terminal to the corresponding terminal of the UPS, and the terminals of the
other end (color: red, black and yellow) to the corresponding terminals of the battery module.
Bat -
Bat-N
PE
Bat-N
Bat -
PE
The cable connection of the positive battery module is shown in Figure 2-27, and the cable connection of the negative
battery module is shown in Figure 2-28.
Chapter 2 Single UPS Installation And Commissioning
Second cell
Third cell
+
+
-
Second cell
Third cell
+
+
-
Figure 2-24 Battery string connection principle diagram 2
600
10
±
900
10
±
Figure 2-25 One-into-multiple battery cables 1 (unit: mm)
1200
10
±
1500
10
±
Figure 2-26 One-into-multiple battery cables 2 (unit: mm)