Figure 2-6. Inserting the Cage Nuts for the Server Faceplate
5. Align one of the Rack Mounting Bracket Assemblies behind the mounting
holes in the vertical mounting rail (see Figure 2-7) located on the left side of
the rack cabinet. The tabs on the front and rear of the Rack Mounting
Bracket Assembly help to align it with the holes in the vertical-mounting
rail.
6. Install two screws (see Figure 2-7) that secure the front of the Rack
Mounting Bracket Assembly to the vertical-mounting rail and tighten
loosely.
7. Carefully align the rear holes of the Rack Mounting Bracket Assembly with
the holes in the rear vertical-mounting rail.
8. Install two screws (see Figure 2-7) that secure the rear of the Rack Mounting
Bracket Assembly to the vertical-mounting rail.
9. Tighten all four screws holding the Mounting Bracket Assembly to the
vertical mounting rails.
Note:
mounting bracket may need to be readjusted.
10. Tighten the six screws securing the two brackets together (see Figure 2-2).
11. Repeat steps 5 through 10 for the mounting the other Rack Mounting
Bracket Assembly on the right side of the rack cabinet.
2-10 Setting Up the System