7.18 Radiation Fin Temperature Rise

L4
Remote
Controller
Display
Outdoor Unit LED
A
Display
Method of
A radiation fin temperature rise is detected by checking the radiation fin temperature with the
Malfunction
compressor on.
Detection
Malfunction
Decision
Conditions
40/50/52/58/68/75 class
80/90 class
Supposed
Causes
Service Diagnosis
j
h
h
h
i
1
2
3
4
The radiation fin temperature with the compressor on is above
The error is cleared when the temperature drops below
A (°C)
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Defective outdoor fan motor
Short circuit
Defective radiation fin thermistor
Disconnection of connector
Defective outdoor unit PCB
Silicon grease is not applied properly on the radiation fin after replacing the outdoor unit
PCB.
h
5
B (°C)
103
95
105
97
Troubleshooting for Outdoor Unit
°C.
A
°C
B