Ol Activation (Compressor Overload) - Daikin 3MKS50E3V1B Service Manual

Super multi nx e / f / g / k-series
Hide thumbs Also See for 3MKS50E3V1B:
Table of Contents

Advertisement

SiBE121135
7.7

OL Activation (Compressor Overload)

E5
Remote
Controller
Display
Outdoor Unit LED
A
Display
Method of
A compressor overload is detected through compressor OL.
Malfunction
Detection
Malfunction
Decision
∗ The operating temperature condition is not specified.
Conditions
Supposed
Causes
Troubleshooting
Check No.01
Refer to P.325
Check No.12
Refer to P.329
Check No.13
Refer to P.330
Check No.14
Refer to P.330
Service Diagnosis
j
i
h
i
h
1
2
3
4
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Defective discharge pipe thermistor
Defective outdoor electronic expansion valve or coil
Defective four way valve or coil
Defective outdoor unit PCB
Refrigerant shortage
Water mixed in refrigerant
Defective stop valve
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Discharge
pipe thermistor
disconnected?
NO
Check No. 01
Check the thermistors.
OK
Check No. 12
Check the outdoor electronic
expansion valve
coil.
OK
Check No. 13
Check the four way
valve.
OK
Check No. 14
Check the refrigerant
line.
OK
h
5
YES
NG
∗ Discharge pipe thermistor
NG
NG
NG
∗ Refrigerant shortage
∗ Water mixed
∗ Stop valve
Troubleshooting for Outdoor Unit
Insert the thermistor in
position.
Replace the discharge pipe
thermistor.
Replace the outdoor
electronic expansion valve
or the coil.
Replace the four way valve
or the coil.
Replace the outdoor unit
PCB.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB.
(R14438)
305

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents