Daikin 3MXS40K2V1B Installation Manual

Daikin 3MXS40K2V1B Installation Manual

R410a split series
Hide thumbs Also See for 3MXS40K2V1B:

Advertisement

INSTALLATION
MANUAL
R410A Split Series
Models
3MXS40K2V1B
3MXS40K3V1B
2MXS52E2V1B
2MXS52E3V1B
3MXS52E2V1B
3MXS52E3V1B
3MXS52E4V1B
3AMX52E2V1B
3AMX52E3V1B
3AMX52E4V1B
2AMX52E2V1B
2AMX52E3V1B
3MKS50E2V1B
3MKS50E3V1B
4MKS58E2V1B
4MKS58E3V1B
Installation manual
R410A Split series
Installationsanleitung
Split-Baureihe R410A
Manuel d'installation
Série split R410A
Montagehandleiding
R410A Split-systeem
Manual de instalación
Serie Split R410A
Manuale d'installazione
Serie Multiambienti R410A
Εγχειρßδιο εγκατÜστασηò
διαιροýìενηò σειρÜò R410A
Manual de Instalação
Série split R410A
Рóêоводство по монтажó
Серия R410A с раздельной óстановêой
Montaj kýlavuzlarý
R410A Split serisi
English
Deutsch
Français
Nederlands
Español
Italiano
ΕλληνικÜ
Portugues
Рóссêий
Türkçe

Advertisement

Table of Contents
loading

Summary of Contents for Daikin 3MXS40K2V1B

  • Page 1 Installationsanleitung Deutsch Split-Baureihe R410A Manuel d’installation Français Série split R410A Montagehandleiding Nederlands R410A Split-systeem Manual de instalación Models Español Serie Split R410A 3MXS40K2V1B 2AMX52E2V1B Manuale d’installazione Italiano 3MXS40K3V1B 2AMX52E3V1B Serie Multiambienti R410A 2MXS52E2V1B 3MKS50E2V1B Εγχειρßδιο εγκατÜστασηò ΕλληνικÜ 2MXS52E3V1B 3MKS50E3V1B διαιροýìενηò σειρÜò R410A...
  • Page 2 3SB64564-17J...
  • Page 3 3SB64564-1...
  • Page 4 3SB65451-5A...
  • Page 5 3SB65451-9D...
  • Page 7: Safety Precautions

    Safety Precautions • The precautions described herein are classified as WARNING and CAUTION. They both contain important information regarding safety. Be sure to observe all precautions without fail. • Meaning of WARNING and CAUTION notices WARNING ..... Failure to follow these instructions properly may result in personal injury or loss of life. CAUTION ....
  • Page 8: Precautions For Selecting The Location

    Accessories Accessories supplied with the outdoor unit: Drain plug Installation Manual There is on the bottom packing case. There is on the bottom packing case. Reducer assembly Screw bag (For fixing electrical wire anchor bands) There is on the bottom packing case. (2MXS52*, 2AMX52*, 3MXS52*, 3AMX52*, 4MKS58*) There is on the bottom packing case.
  • Page 9: Indoor/Outdoor Unit Installation Drawings

    Indoor/Outdoor Unit Installation Drawings For installation of the indoor units, refer to the installation manual which was provided with the units. (The diagram shows a wall-mounted indoor unit.) CAUTION • Do not connect the embedded branch piping and the outdoor unit when only carrying out piping work without connecting the indoor unit in order to add another indoor unit later.
  • Page 10: Connections (Connection Port)

    Installation • Install the unit horizontally. • The unit may be installed directly on a concrete verandah or a solid place if drainage is good. • If the vibration may possibly be transmitted to the building, use a vibration-proof rubber (field supply). Connections (connection port) Install the indoor unit according to the table below, which shows the relationship between the class of indoor unit and the corresponding port.
  • Page 11: Outdoor Unit Installation Guideline

    Outdoor Unit Installation Guideline • Where a wall or other obstacle is in the path of outdoor unit’s inlet or outlet airflow, follow the installation guidelines below. • For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less. Walls facing two sides Wall facing one side More than 100...
  • Page 12: Refrigerant Piping Work

    Refrigerant Piping Work Installing outdoor unit 1) When installing the outdoor unit, refer to “Precautions for Selecting the Location” and the “Indoor/Outdoor Unit Installation Drawings”. 2) If drain work is necessary, follow the procedures below. Drain work 1) Use the drain plug for drainage. 2) If the drain port is covered by a mounting base or floor surface, place Drain-water hole additional foot bases of at least 30mm in height under the outdoor...
  • Page 13: Purging Air And Checking Gas Leakage

    Purging air and checking gas leakage WARNING • Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle. • When refrigerant gas leaks occur, ventilate the room as soon and as much as possible. • R410A, as well as other refrigerants, should always be recovered and never be released directly into the environment. •...
  • Page 14: Charging With Refrigerant

    Refrigerant Piping Work Refilling the refrigerant Check the type of refrigerant to be used on the machine nameplate. Precautions when adding R410A Fill from the gas pipe in liquid form. It is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal operation. 1) Before filling, check whether the cylinder has a siphon attached or not.
  • Page 15 Refrigerant piping work Wall Be sure to place a cap. Cautions on pipe handling Rain If no flare cap is 1) Protect the open end of the pipe against dust and moisture. available, cover the flare mouth 2) All pipe bends should be as gentle as possible. Use a pipe bender for with tape to keep bending.
  • Page 16: How To Use Reducers

    How to Use Reducers No.1 No.2 No.3 No.4 No.5 No.6 φ15.9 φ12.7 φ15.9 φ12.7 φ15.9 φ15.9 → φ12.7 → φ9.5 → φ12.7 → φ9.5 → φ9.5 → φ9.5 Gasket (1) Gasket (2) Reduce and gasket Use the reducers supplied with the unit as described below. 1) Connecting a pipe of φ12.7 to a gas pipe connection port for φ15.9: No.
  • Page 17: Pump Down Operation

    Pump Down Operation In order to protect the environment, be sure to pump down when relocating or disposing of the unit. 1) Remove the valve cap from liquid stop valve and gas stop valve. Close 2) Carry out forced cooling operation. 3) After five to ten minutes, close the liquid stop valve with a Hexagonal hexagonal wrench.
  • Page 18 Wiring WARNING • Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical shock, or fire. • Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the terminal block.) Doing so may cause electric shock or fire.
  • Page 19: Priority Room Setting

    Priority Room Setting • To use priority room setting, initial settings must be made when the unit is installed. Explain the priority room setting, as described below, to the customer, and confirm whether or not the customer wants to use priority room setting. Setting it in the guest and living rooms is convenient.
  • Page 20: Night Quiet Mode Setting

    Night Quiet Mode Setting • If night quiet mode is to be used, initial settings must be made when the unit is installed. Service PC-board Explain night quiet mode, as described below, to the customer, and confirm whether or not the customer wants to use night quiet mode.
  • Page 21: Trial Operation And Testing

    Trial Operation and Testing • Before starting the test run, measure the voltage at the primary side of the safety breaker. Check that it is 220-240V. • Check that all liquid and gas stop valves are fully open. • Check that piping and wiring all match. The wiring error check can be conveniently used for underground wiring and other wiring that cannot be directly checked.
  • Page 22: Items To Check

    Trial Operation and Testing Trial operation and testing 1) To test cooling, set for the lowest temperature. To test heating, set for the highest temperature. (Depending on the room temperature, only heating or cooling (but not both) may be possible.) 2) After the unit is stopped, it will not start again (heating or cooling) for approximately 3 minutes.
  • Page 23 Two-dimensional bar code is a code for manufacturing. 3P164392-4P M11B057B (1210) HT...