5. Wiring
5.1 Preparation before Wiring
1.
Ensure voltage values and polarities are correct.
2.
When grounding the solar array, an isolation transformer is required due to
the RPI-series not having galvanic isolation between the DC-input and
AC-output.
3.
The ground fault detection is a fixed internal setting. It cannot be modified.
4.
Whole system wiring and connections can be seen in Figure 5-1 and 5-2.
5.
Inverter can accept DC inputs in parallel (1 MPP tracker/2 parallel inputs).
6.
Different DC connection type needs different settings of insulation detection.
About setting, please refer to 7.2.6.3 Install Setting.
* Some models can support 3P3W
system, please refer to table 5-3.