Maximum short circuit
current per MPPT (Isc)
AC OUTPUT (GRID SIDE)
Nominal power
Maximum power
Voltage
Nominal current
Maximum current
Inrush current
Maximum output fault
current (rms)
Maximum output overcurrent
protection
Frequency
Total harmonic distortion
Power factor
DC current injection
Tare loss
Maximum efficiency
EU efficiency
AC connector
Fuse
SYSTEM INFORMATION / COMMUNICATION
User interface
Externalcommunication
24 A
8kVA
8.4kVA
3Ph, 230/400Vac (3phase / N / PE)
11.6 A
12.8 A
150A/100μs
22 A
16 A
50 Hz model: 47 – 53 Hz
60 Hz model: 57 – 63 Hz
> 0.99 @ full power
Adjustable: 0.80 leading – 0.80 lagging
<0.5% rated current
98.2%
97.4%
3 Ph + N + PE; 3-phase AC plug that meets IP67
and specifications in table 5-2.
N/A. Please connect to an external protection
device (1.25 rated current)
Black-on-white graphical LCD display
365 days data logger and real time clock
30 events record
2 RS-485 connections
24 A
10kVA
10.5kVA
14.5 A
16 A
150A/100μs
150A/100μs
22 A
20 A
< 3 %
<2 W
98.3%
97.7%
24 A
12kVA
12.6kVA
17.4A
19.2 A
22 A
25 A
98.3%
97.7%