to shift the borderline 2 if the generating plant's connection concept requires to
do so. Also in consultation with the network operator, a short-time disconnection
from the network is permissible if the generating plant can be resynchronized 2
seconds, at the latest, after the beginning of the short-time disconnection. After
resynchronization, the active power must be increased with a gradient of at least
10% of the nominal capacity per second (TC2007; 3.3.13.5, section 14).
Figure 6-4 Borderlines of the voltage profile of a type-2 generating plant at the network
RPI-M8/ M10/ M12/ M15/ M15A/ M20/ M20A/ M30 implements the FRT behavior
as the figure below, in area
1.
Keep normally operate
2.
Feed-in reactive current according to ΔU/Un and K factor
3.
Short-time disconnect
4.
Long-time disconnect
I
B
-10
K factor
connection point
/I
n
U
100%
K factor
U2
+10
U/Un
U1
Udrop

Figure 6-5 FRT characteristic

U
grid/
nom
1
2
0
t1
t2
Fault occurence
3
4
t3
time