Wolf BWL-1 S Installation And Operating Instructions Manual page 64

Split air/water heat pump
Table of Contents

Advertisement

Contractor
Description
parameter
WP015
WP016=On:
For setting the maximum speed of the feed/heating circuit pump (ZHP).
WP016=Off:
For setting the constant speed of the feed/heating circuit pump (ZHP).
WP016
Enables spread control (controlling to set spread WP010) and PWM actuation
(WP015) of the feed/heating circuit pump (ZHP).
WP017
For setting the max. flow temperature limit (T_boiler).
With screed drying function for setting the maximum temperature.
WP018
For setting the min. flow temperature limit (T_boiler).
With screed drying function for setting the constant temperature.
WP020
For setting the hysteresis value for DHW heating or DHW cylinder heating.
WP021
Enables a maximum heating time for the DHW cylinder.
WP022
For setting the maximum heating time for the DHW cylinder.
WP023
For setting the delay time for activation of the electric heating / additional heat
generator for DHW heating.
WP024
For setting the minimum DHW temperature for ECO mode.
WP025
Enables the smart grid function.
WP026
For raising the set flow temperature (T_Boiler set) for heating mode so that the heat
pump is activated at a defined point.
WP027
For raising the set DHW temperature (T_DHW set) so that the heat pump is activated
at a defined point.
WP028
For selecting whether an activation command via smart grid switches on just the
compressor, or the compressor plus the electric heating.
WP031
If multiple heat sources are controlled in one heating system with a cascade module,
addresses must be allocated to the heat sources.
WP053
For setting the minimum outside temperature for active cooling mode.
WP054
For setting the minimum flow temperature (T_boiler) of the actively cooled heating
circuits.
WP055
For setting the offset value or the differential between the outside temperature and
the set flow temperature (T_Boiler set) of the actively cooled heating circuits.
(T_Boiler set = T_outside - Offset (WP055)).
WP058
Enable function for active cooling.
WP080
Dual mode point for deactivation of the compressor.
WP090
Enables the electric heating for heating mode.
WP091
Dual mode point for activation of electric heating for heating mode
WP092
For setting power-OFF for the electric heating.
WP093
Deactivation of the dual mode point (WP091) of the electric heating for the set period.
Serves the screed drying function, to ensure that the electric heating supports the
heat pump.
WP094
For setting the installed electric heating or setting the actual installed connected load
of the electric heating.
WP101
Dual mode point for activation of the additional heat generator.
WP121
Serves to limit the compressor start-ups per hour.
64
31. Contractor level
3064298_201507