Connection, HCP (230 V AC; max. 1.5 A) *
Push connecting cable through cable entry.
Connect the connecting cable to terminals L1, N and
* M ax. 1.5 A / 345 VA per output, sum of all outputs no more
than 600 VA
Connection, 3WUV heating / cooling
(230 V AC; max.1.5A) *
Push connecting cable through cable entry.
Connect the connecting cable to terminals L1, N and
* M ax. 1.5 A / 345 VA per output, sum of all outputs no more
than 600 VA
Connection, output A1 (230 V AC; max. 1.5 A) *
Push connecting cable through cable entry.
Connect the connecting cable to terminals L1, N and
* M ax. 1.5 A / 345 VA per output, sum of all outputs no more
than 600 VA
Changing the fuse
Isolate the heat pump from the power supply prior to changing
a fuse.
The ON/OFF switch on the appliance does not provide
separation from the power supply.
The fuse is located under the top casing cover of the control
unit (HCM-3).
Danger due to live electrical components. Never touch
electrical components or contacts if the heating appliance has
not been isolated from the power supply. Risk to life!
42
25. Power supply to the indoor module
.
.
.
Fig: HCP connection
Fig: 3WUV connection
Fig: Output A1 connection
Fig: Changing the fuse
3
3
3
M4A
T4A
HCM-2
Fuse
5x20
Netz
Z1
ZHP
A1
LP
L1
N
L1
L1
L1
N
L1