Wolf BWL-1S-05 Installation And Operating Instructions Manual

Wolf BWL-1S-05 Installation And Operating Instructions Manual

Split air/water heat pump
Hide thumbs Also See for BWL-1S-05:
Table of Contents

Advertisement

Quick Links

Installation and operating instructions
Split air/water heat pump
BWL-1S -05/230 V
BWL-1SB -05/230 V
BWL-1S -07/230 V
BWL-1SB -07/230 V
BWL-1SB -10/230 V
BWL-1SB -14/230 V
From:
2016 appliance version
HCM-3 FW 1.70
AM
FW 1.60
BM-2
FW 2.30
WOLF GMBH / P.O. BOX 1380 / D-84048 MAINBURG / TEL. +49(0) 87 51 74- 0 / FAX +49(0) 87 51 74- 16 00 / www.wolf.eu
Doc. no.: 3064298_201805
Integrated system log book
BWL-1S -10/400 V
BWL-1SB -10/400 V
BWL-1S -14/400 V
BWL-1SB -14/400 V
BWL-1S -16/400 V
BWL-1SB -16/400 V
Subject to modifications
GB

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the BWL-1S-05 and is the answer not in the manual?

Questions and answers

Summary of Contents for Wolf BWL-1S-05

  • Page 1 2016 appliance version HCM-3 FW 1.70 FW 1.60 BM-2 FW 2.30 WOLF GMBH / P.O. BOX 1380 / D-84048 MAINBURG / TEL. +49(0) 87 51 74- 0 / FAX +49(0) 87 51 74- 16 00 / www.wolf.eu Doc. no.: 3064298_201805 Subject to modifications...
  • Page 2: Table Of Contents

    Table of contents Table of contents Safety instructions / standards and regulations ............6 Safety information ........................6 Standards / regulations ......................7 The following regulations and directives must be observed when carrying out installation, commissioning, maintenance and repair work: ................ 8 Documentation information ...................9 Other applicable documents ....................9 Safekeeping of these documents ..................... 9 Applicability of these instructions .....................
  • Page 3 Table of contents Filling the refrigerant lines ...................30 16.1 Filling the indoor module and refrigerant lines ............... 30 16.2 Checking the refrigerant circuit for leaks ................30 Connecting the heating/DHW circuit ................31 17.1 Observe the following points for the heating/DHW circuit ............31 17.1.1 Air vent valve ......................... 31 17.1.2 Flushing the heating system ....................
  • Page 4 Table of contents 24.4 Standard settings ........................53 24.5 Description ..........................54 24.5.1 DHW operating mode ......................54 24.5.2 DHW quick heat-up ........................ 54 24.6 Energy saving mode ......................54 24.6.1 Active cooling ......................... 54 BM-2 programming unit ....................55 25.1 Overview ..........................55 25.2 Menu structure ........................
  • Page 5 Table of contents 29.2.10 System configuration 34 ......................81 29.2.11 System configuration 51 ......................82 29.2.12 System configuration 52 ......................83 Additional functions .....................84 30.1 Active cooling ......................... 84 30.2 Power-OFF ..........................84 30.3 PV increase ..........................85 30.4 Smart Grid (SG) ........................86 30.5 Calculating set temperatures when raising the temperature via PV or Smart Grid....87 Sound level ........................88 31.1 The following must be observed when installing the system ..........
  • Page 6: Safety Instructions / Standards And Regulations

    Safety i nstructions / s tandards a nd r egulations Safety instructions / standards and regulations 1.1 Safety information The following symbols are used in this description to highlight important information concerning personal and operational safety: Denotes instructions with which you must strictly comply to prevent risk or injury to individuals, faults or damage to the appliance.
  • Page 7: Standards / Regulations

    Safety i nstructions / s tandards a nd r egulations 1.2 Standards / regulations Observe all standards and guidelines applicable to the installation and operation of this heating system in your country. Observe the information on the heat pump type plate. The following local regulations must be complied with during installation and operation of the heating system: • Siting conditions • Electrical connection to the power supply • The regulations and standards regarding the safety equipment of the water heating system •...
  • Page 8: The Following Regulations And Directives Must Be Observed When Carrying Out Installation, Commissioning, Maintenance And Repair Work

    When siting the heat pump, position and install it securely, to prevent it slipping or sliding during operation. The outdoor unit may only be installed outdoors. Only replace faulty components with original WOLF spare parts. Observe specified electrical fuse ratings (see specification). Any damage or loss resulting from technical modifications to WOLF control units is excluded from our warranty.
  • Page 9: Documentation Information

    Documentation information Documentation information 2.1 Other applicable documents f Installation and operating instructions for BM-2 programming unit f Installation and operating instructions for AM display module f Installation and operating instructions for all accessory modules and further accessories used 2.2 Safekeeping of these documents The system operator or user should ensure the safekeeping of all documentation. f Hand over these installation and operating instructions, along with all other applicable documents, to the system operator or user.
  • Page 10: Information On The Heat Pump

    Information on the heat pump Information on the heat pump Application range The split air/water heat pump for heating water temperatures up to 55 °C and air temperatures down to -20 °C is designed exclusively to heat heating water and domestic hot water. The heat pump can be used in new or existing heating systems, provided the application limits are taken into consideration (see "Specification").
  • Page 11 Other equipment features The appliance is equipped with sensors that monitor the heating circuit and the refrigerant circuit. DHW cylinders WOLF heat pumps require special DHW cylinders for heating the domestic hot water; these are available from the WOLF range of accessories. Please The indirect coil surface area in the DHW cylinders must be at least 0.25 m² per kW of heating...
  • Page 12: Standard Delivery

    Standard delivery Standard delivery f Outdoor module, fully encased in box f Indoor module, fully encased in box, containing the following: − Installation and operating instructions including system log book and maintenance instructions − Commissioning report with checklist − Suspension bracket and installation kit for indoor module −...
  • Page 13: Structure

    Structure Structure 5.1 BWL-1S(B) indoor module Boiler water temperature sensor Air vent valve (AWO T_boiler) Control unit and electrical Condenser connection in integral casing Electric booster heater (accessory for BWL-1SB) Heating circuit pressure sensor Refrigerant pressure sensor (Refrigerant temp. (ICT)) Pressure gauge High efficiency heating circuit pump Heating circuit flow sensor Schrader valve...
  • Page 14: Bwl-1S(B)-05/07 Outdoor Module

    Structure 5.2 BWL-1S(B)-05/07 outdoor module OAT: evaporator air intake temperature sensor Evaporator (T_supply air/supply air temperature) Inverter with PCB OMT: evaporator temperature sensor (T_evaporator/evaporator temperature) Electrical connection 4-way valve pHi: high pressure switch CTT: compressor head temperature sensor (T_hot gas/hot gas temperature) OCT: Ee Liquid separator Compressor...
  • Page 15: Equipment Features

    Equipment features Equipment features 6.1 Indoor module • Demand-controlled electric booster heater For 2/4/6 kW depending on connection – type BWL-1S For covering peak loads Adjustable for emergency mode or for screed drying Screed drying also possible without outdoor module • Control unit and electrical connection in integral casing •...
  • Page 16: Bwl-1S(B) Dimensions

    BWL-1S(B) dimensions BWL-1S(B) dimensions 7.1 Indoor module Electrical connection 3064298_201805...
  • Page 17: Bwl-1S(B)-05/07 Outdoor Module

    BWL-1S(B) dimensions 7.2 BWL-1S(B)-05/07 outdoor module 7.3 BWL-1S(B)-10/14/16 outdoor module 3064298_201805...
  • Page 18: Siting The Bwl-1S(B)

    Siting the BWL-1S(B) Siting the BWL-1S(B) 8.1 Siting instructions When selecting the installation site, observe the following points: - The heat pump must be accessible on all sides The intake area should preferably be on a wall. - The air discharge side must be free from obstruction. Since the air being discharged is around 8 K colder than the ambient temperature, premature ice formation should be expected.
  • Page 19: Minimum Room Volume

    Siting the BWL-1S(B) 8.2 Minimum room volume When siting the heat pump in occupied/communal areas, as opposed to a separate plant room, the minimum room volume in relation to the refrigerant charge weight must be complied with. In accordance with EN 378-1, the following limit applies to R410A refrigerant: 0.44 kg/m³ refrigerant per cubic metre room volume. For refrigerant lines less than 12 m, the refrigerant charge weight provided is sufficient. For refrigerant lines between 12 m and a maximum of 25 m long, an additional 0.06 kg/m of R410A needs to be added;...
  • Page 20: Siting The Outdoor Module

    Siting the outdoor module Siting the outdoor module Minimum clearances for the outdoor module Fig.: Front view of outdoor module BWL-1S(B)-10/14/16 Fig.: Front view of outdoor module BWL-1S(B)-05/07 Air intake Air intake ≥100 ≥100 ≥500 ≥500 Air discharge Air discharge Fig.: Plan view of outdoor module BWL-1S(B)-10/14/16 Fig.: Plan view of outdoor module BWL-1S(B)-05/07 Air discharge a ≥ 1000 to obstacles obstructing the air discharge; a ≥ 3000 to footpaths and patios due to the formation of ice, even when outside temperatures are above 0 °C. Clearance between outdoor module and ground In areas with heavy snowfall, the minimum installation height must be increased or a canopy must be constructed over the outdoor module.
  • Page 21: Siting The Indoor Module

    Siting the indoor module 10 Siting the indoor module 10.1 Minimum clearances for the indoor module ≥ 40 ≥ 40 Fig.: Plan view of indoor module Fig.: Front view of indoor module 10.2 Securing the appliance with the suspension bracket When installing the appliance, ensure that the fixings have sufficient load bearing capacity. In addition, take into account the condition of the wall, otherwise refrigerant and water could escape, resulting in a risk of flooding. 1. Mark the Ø12 holes to be drilled for the suspension bracket, taking into account the minimum clearances. 2. Insert the rawl plugs and fit the suspension bracket using the screws supplied. 3.
  • Page 22: Gravel Bed And Foundation Diagram

    Gravel bed and foundation diagram 11 Gravel bed and foundation diagram Base for floorstanding installation BWL-1S(B)-05/07 175 mm 30 mm BWL-1S(B)-10/14/16 250 mm 105 mm A Gravel bed as condensate soakaway B Frost protection base for foundation (compressed gravel, e.g. 0 – 32/56 mm), layer thickness in accordance with local conditions and applicable building regulations C Foundation strip D KG pipe DN 100 with 2 pipe bends 45°...
  • Page 23: Anchorage And Anti-Vibration Mounts

    Anchorage and anti-vibration mounts 12 Anchorage and anti-vibration mounts 12.1 Concrete foundation Tighten the nuts of the rubber mounts till about 8 mm of rubber is visible 8 mm Cast, level plinth of concrete with gravel base providing sufficient frost protection, cut-out for cable/line entry, see foundation diagram Secure in accordance with structural characteristics, taking into account Please the appliance weight. note 12.2 Wall mounting Tighten the nuts of the rubber mounts till about 8 mm of rubber is visible...
  • Page 24: Routing The Wall Duct

    Routing the wall duct 13 Routing the wall duct 13.1 Wall duct above ground level Observe minimum distance from building wall Please note: The wall mounting bracket can only be used on walls with a high mass per unit area (> 250 kg/m²). Lightweight walls or stud walls are not permitted. BWL-1S(B)-05/07 175 mm BWL-1S(B)-10/14/16 250 mm Pipe clamp with EPDM lining 13.2 Wall duct below ground level Observe minimum distance from building wall BWL-1S(B)-05/07 175 mm BWL-1S(B)-10/14/16 250 mm 3064298_201805...
  • Page 25: Routing The Refrigerant Lines

    Routing the refrigerant lines 14 Routing the refrigerant lines The outdoor module is pre-charged with refrigerant R410A. No additional charge is required for lines up to 12 m in length. Minimum line length 3 m, maximum line length 25 m. Max. height differential between indoor and outdoor unit 15 m. For 12 – 25 m line length, top up with 60 g/m of refrigerant R410A. Use only copper pipes suitable for refrigerants to EN-12735-1, and thermal insulation with a temperature resistance of up to 120 °C. (For internal diameter, see "Specification" chapter.) Suction gas lines and liquid lines must have separate thermal insulation. Closed cell, diffusion-proof thermal insulation, min.
  • Page 26 Routing the refrigerant lines Height differentials If the height differential between the indoor and the outdoor units is > 4 m, both refrigerant lines will require oil lift bends to prevent oil shortages in the compressor. Outdoor module higher than indoor module Cooling mode Heating mode Suction line Hot gas line Oil lift bend (gaseous) (gaseous)
  • Page 27: Connecting The Refrigerant Lines

    Liquid line Ø 6 mm or 1/4 inch 7/16 UNF 16 ± 2 Hot gas line Ø 12 mm or 1/2 inch 3/4 UNF 56 ± 6 BWL-1S(B)-07/10/14/16 Liquid line Ø 10 mm or 3/8 inch 5/8 UNF 37 ± 4 Hot gas line Ø 16 mm or 5/8 inch 7/8 UNF 70 ± 7 Euro flanged adaptor connection kit for 10 and 16 mm Ø Alternatively, the refrigerant lines can also be connected using the Euro flanged adaptor connection kit for hard-soldering on refrigerant lines (lines must be flushed with nitrogen), available from the WOLF range of accessories. 3064298_201805...
  • Page 28: Connecting The Refrigerant Line To The Indoor Module

    − Remove the nuts from the liquid line and hot gas line connections of the refrigerant lines. − Slide the supplied nuts over the copper pipes. − Flare the copper pipes. − The Euro flanged adaptor connection kit, available from the WOLF range of accessories, can be used as an alternative to flaring for the Ø 10 mm and Ø 16 mm lines − Do not allow any contaminants (e.g. metal swarf or moisture) to enter the copper pipes.
  • Page 29: Leak And Pressure Testing

    Suitable personal protective equipment must be used when handling refrigerant. Refrigerant R410A used in WOLF split heat pumps is an air-displacing, non-toxic gas. Uncontrolled release of refrigerant may result in breathing difficulties and asphyxiation. Observe the corresponding regulations and guidelinesfor handling this refrigerant.
  • Page 30: Filling The Refrigerant Lines

    Filling the refrigerant lines 16 Filling the refrigerant lines 16.1 Filling the indoor module and refrigerant lines Single refrigerant line length < 12 m The pre-filled quantity of refrigerant in the outdoor module is sufficient for a single line length of 3 to 12 m. Single refrigerant line length > 12 m Line lengths of 12 - 25 m must be topped up with an additional 60 g/m of refrigerant R410A. The additional refrigerant can be added after evacuating the refrigerant lines and before opening the shut-off valves on the outdoor module.
  • Page 31: Connecting The Heating/Dhw Circuit

    Connecting the heating/DHW circuit 17 Connecting the heating/DHW circuit 17.1 Observe the following points for the heating/DHW circuit Connection for the ventilation hose Return, heating / DHW 28 x 1 Flow, heating 28 x 1 Hose, safety valve DN 25 Flow, DHW 28 x 1 17.1.1 Air vent valve An air vent valve must be installed at the highest point in the system. 17.1.2 Flushing the heating system The following points must be observed for the heating side: −...
  • Page 32: Draining The Heating System

    Connecting the heating/DHW circuit 17.1.4 Draining the heating system - Shut down the system. Risk of scalding Hot water can cause severe scalding. Before working on water-seated parts, allow the appliance to cool to below 40 °C, shut off all valves and, if necessary, drain the appliance. Risk of burns Hot components can cause burns.
  • Page 33: Dirt Trap

    Connecting the heating/DHW circuit 17.1.12 Dirt trap To protect the heat pump, a dirt trap must be installed in the heating return. Installing dirt traps or carrying out any other modifications in the supply line to the safety valve is not permitted. WOLF recommends a sludge separator with magnetite separator to protect the appliance and the high efficiency pump from dirt/sludge and magnetite. 17.1.13 Dew point monitor (DPM) A dew point monitor (accessory) is required for area cooling systems (e.g. underfloor heating circuit, cooling ceiling). If the cooling circuit serves several rooms with different relative humidities, several dew point monitors must be installed and connected in series. The monitors are fitted to the cooling circuit flow in the room to be cooled. Remove the thermal insulation from this area. You can set the dew point monitor switching point to between 75 % and 100 % relative humidity using a potentiometer (factory setting is 90 % rh).
  • Page 34: Chc Split / 200 Heat Pump Centre

    18 CHC Split / 200 heat pump centre 18.1 CHC Split / 200 The BWL-1S-05/07/10/14/16 can be combined with the CEW-2-200 DHW cylinder and PU-35 buffer cylinder to form a heat pump centre. The series buffer cylinder ensures the necessary defrost energy is available. BWL-1S-200 mit PU 35 Vorderansicht 18.2 Dimensions / minimum clearances...
  • Page 35: Chc Split / 300 Heat Pump Centre

    19 CHC Split / 300 heat pump centre 19.1 CHC Split / 300 The BWL-1S-05/07/10/14/16 can be combined with the SEW-2-300 DHW cylinder and PU-50 buffer cylinder to form a heat pump centre. The PU-50 buffer cylinder can be installed as a series or separating buffer and ensures the necessary defrost energy is available Mindestabstände Vorderansicht BWL-1S-300...
  • Page 36: Electrical Connection

    Electrical connection 20 Electrical connection 20.1 General information The installation may be carried out only by an approved electrical contractor. Observe VDE regulations [Germany] and all local regulations of your power supply utility. An omnipolar isolator with at least 3 mm contact separation must be integrated in the power cable upstream of the appliance. If using residual current protection (ground fault circuit interrupter or RCD), use a type B AC/DC-sensitive residual current protective device, as this is the only type suited to DC residual currents. Type A residual current protective devices are not suitable. Do not route sensor leads alongside 230 V or 400 V cables. Danger through 'live' electrical components. Please note: Turn OFF the ON/OFF switch before removing the casing. Never touch electrical components or contacts when the ON/OFF switch is in the ON position. There is a danger of electrocution, resulting in a risk to health or death. The main terminals are "live", even when the ON/OFF switch is in the OFF position. During servicing and installation work, isolate the entire system from the power supply across all poles, otherwise there will be a risk of electrocution. Before connecting the appliance to the power supply, ensure that all electrical covers and protective devices are fully installed. Connecting cables, installation ducts or tubes, etc., must be weatherproof, UV-resistant and protected from mechanical damage. Front panel with integral ON/OFF switch 3064298_201805...
  • Page 37: Mains Feed / Connection

    Electrical connection 20.2 Mains feed / connection Indoor module (IDU) Outdoor module (ODU) Control 230 V/50 Hz ODU bus Electric heater 230 V/50 Hz Electric heater 400 V/50 Hz On-site connections Power supply utility, Outdoor module PV / Smart Grid BWL-1S(B)-05/07 / 230 V BWL-1S(B)-05/07 indoor module Outdoor module 230 V/50 Hz Control 230 V/50 Hz ODU bus Electric heater 230 V/50 Hz Electric heater 400 V/50 Hz On-site connections Power supply utility, PV / Smart Grid Indoor module Outdoor module BWL-1S(B)-10 BWL-1S(B)-10 / 400 V Outdoor module 400 V/50 Hz Outdoor module BWL-1S(B)-10 / 230 V...
  • Page 38: Outdoor Module Electrical Connection

    Outdoor module electrical connection 21 Outdoor module electrical connection 21.1 Opening the BWL-1S(B)-05/07 outdoor module casing BWL-1S(B)-05/07 21.2 BWL-1S(B)-05/07 outdoor module electrical connection * See "Specification" for fuse protection values. The ODU bus connection (12 V) must be routed separately from 230 V/400 V cables. Only one bus may be connected. BWL-1S(B)-05/07/230 V 230 V~ Indoor module terminal strip X1 ODU bus 12 V Mains (2x0.75 mm , screened) 3064298_201805...
  • Page 39: Opening The Bwl-1S(B)-10/14/16 Outdoor Module Casing

    Outdoor module electrical connection 21.3 Opening the BWL-1S(B)-10/14/16 outdoor module casing BWL-1S(B)-10 BWL-1S(B)-14 BWL-1S(B)-16 21.4 BWL-1S(B)-10/14/16 outdoor module electrical connection * See "Specification" for fuse protection values. The ODU bus connection (12 V) must be routed separately from 230 V/400 V cables. Only one bus may be connected. BWL-1S(B)-10/400 V BWL-1S(B)-10/230 V BWL-1S(B)-14/400 V BWL-1S(B)-14/230 V BWL-1S(B)-16/400 V 230 V~ 230 V~ Indoor module Indoor module Terminal strip X1 Terminal strip X1 ODU bus ODU bus 12 V 12 V Mains Mains (2x0.75 mm , screened) (2x0.75 mm , screened)
  • Page 40: Indoor Module Electrical Connection

    Indoor module electrical connection 22 Indoor module electrical connection 22.1 Opening / unhooking the indoor module casing Opening the integral casing cover Cable entry / Cable entry electrical connection Terminal strip X1 Contactor for electric heater HCM-3 PCB with cover AWO/EWO communication board 3064298_201805...
  • Page 41: Electric Heater Connection

    Indoor module electrical connection 22.2 Electric heater connection Output 3way DV heating/DHW PSU, PV / Smart Grid 230 V~ ODU bus GTS (appliance type connector) * See "Specification" for fuse protection values. 6/9 kW 4/6 kW 2/3 kW On the BWL-1S with integral 3-phase electric heater, the heater connection can be either single phase, 2-phase or 3-phase. Depending on demand, the control unit activates the electric heater via a contactor.
  • Page 42: Psu / Pv / Smart Grid / Odu Bus Connection

    Indoor module electrical connection 22.3 PSU / PV / Smart Grid / ODU bus connection (See also "Additional functions" chapter.) Electric heater Smart* feed Grid Output 3way DV Power- heating/DHW 230 V~ increase Power-OFF, PV / Smart Grid BWL-1S(B) 05/07/10/14/16 ODU bus GTS (appliance type connector) (2x0.75 mm , screened) * Floating contacts Notes: −...
  • Page 43 Indoor module electrical connection Example 2: Power supply with power-OFF, with on-site load disconnection Indoor module Outdoor module (IDU) (ODU) Control 230 V/50 Hz ODU bus Electric heater 230 V/400 V/50 Hz On-site connections X1-9/10 (power-OFF) BWL-1S(B)-05/07/10/14/16 Outdoor module 230 V/400 V/50 Hz 230 V/400 V Ripple control receiver (floating contact) Switching device(s) / contactor(s) * Provide switching device(s) / contactor(s) and control voltage on site Notes:...
  • Page 44: Pcb Connection

    Netz Netz 1 2 + - Figure: HCM-3 PCB eBUS 1(+), 2(-) WOLF control accessories SF (5 k NTC cylinder sensor) AF (5 k NTC outside sensor) E2/SAF (5 k NTC header sensor SAF; alternatively 0-10 V activation by e.g. BMS or activation via floating contact)
  • Page 45: Electrical Connection (230 V)

    Indoor module electrical connection 22.5 Electrical connection (230 V) 230 V mains connection Netz The control and safety devices are fully wired and tested. You only need to connect the power supply and the external accessories. Create a permanent connection for the power supply. Provide the power supply via a mains isolator (e.g. heating system emergency stop switch) that ensures at least 3 mm contact separation for all poles.
  • Page 46 Indoor module electrical connection Connecting the HCP (230 V AC; max. 1.5 A) * Netz Push connecting cable through cable entry. Connect the cable to terminals L1, N and * Max. 1.5 A / 345 VA per output; sum of all outputs no more than 600 VA Figure: HCP connection Connection, 3-way diverter valve, heating/cooling (230 V AC; max. 1.5 A) * Netz Push connecting cable through cable entry.
  • Page 47: Electrical Connection (Low Voltages)

    SF, as this will destroy the component. note Figure: Cylinder sensor SF connection Connecting digital WOLF control accessories (e.g. BM-2, MM, KM, SM1, SM2) Only controllers from the WOLF range of accessories may be connected. Each accessory is supplied with its own 230 V~ connection diagram. Use a two-core cable (cross-section > 0.5 mm²) as the connecting cable between the control accessory and the BWL-1S (1 is + and 2 is -).
  • Page 48: Indoor Module Hcm-3 Pcb Wiring Diagram

    Indoor module electrical connection 22.7 Indoor module HCM-3 PCB wiring diagram 3-way diverter valve heating/cooling Control feed E2/SAF eBUS Netz Electric heater 3064298_201805...
  • Page 49: Indoor Module Ewo Board / Awo Board Wiring Diagram

    Indoor module electrical connection 22.8 Indoor module EWO board / AWO board wiring diagram EWO board / AWO board 3064298_201805...
  • Page 50: Am Display Module / Bm-2 Programming Unit

    • AM is always in the heating appliance Installation Insert the AM display module or BM-2 programming unit in the slot above the ON/OFF switch (WOLF logo). Switch ON power supply / MCB and switch ON/OFF switch to ON. Notes: From software version FW 1.40*, the BWL-1S(B) split air/water heat pumps can be operated directly using a BM-2 programming unit (from software version FW 2.10**) installed in the indoor unit.
  • Page 51: Am Display Module

    AM display module 24 AM display module 24.1 Overview Note: Other functions and descriptions can be found in the installation instructions for contractors or the user operating instructions for the AM display module. Status display Quick start keys Key 1 Heating appliance Boiler water temperature Key 2 Rotary selector with 38.0 °C pushbutton function System pressure Key 3 1.5 bar Key 4 Set heating temperature Key 1 (if BM-2 as remote control - no function) Set DHW temperature Key 2 (if BM-2 as remote control - no function) Key 3 Display of outdoor unit system data selection Key 4 Acknowledge fault / Finish / Back Outdoor unit Current appliance output 27 % Comp.
  • Page 52: Menu Structure

    AM display module 24.2 Menu structure Only those menu items are shown that are relevant to the system concerned. Message Heating appliance Status Display of Boiler water Operating mode faults temperature HP status System pressure Main menu Back Displays Standard settings Contractor Back 3064298_201805...
  • Page 53: Displays

    AM display module 24.3 Displays In the AM "Displays" submenu, the following real-time statuses and measured values, as well as statistical system data, can be retrieved. Values are displayed according to system type and configuration. Designation Unit Meaning T_boiler °C Flow temperature T_boiler set °C Flow temperature (set value) System pressure Secondary pressure/heating circuit pressure T_outside °C Outside temperature...
  • Page 54: Description

    AM display module 24.5 Description (Selection and more details in the AM display module instructions.) 24.5.1 DHW operating mode Comfort setting: In the Comfort setting, the heat pump tries to reach the set DHW temperature. After the delay period (WP013/WP023) has elapsed, the electric heater/additional heat generator is activated. When the compressor's application limit is reached (FL/RTN >...
  • Page 55: Programming Unit

    BM-2 programming unit 25 BM-2 programming unit 25.1 Overview Note: Further functions and descriptions can be found in the installation instructions for contractors or the user operating instructions for the BM-2 programming unit. Screen header Operating mode HP status Quick start keys Heating appliance Rotary selector Heating mode with pushbutton Operation System data display function 1.94bar (content varies) Pressure 25.2 °C Electric heater status Boiler Compressor status 20.01.2013 14:12 (symbol content varies according to current...
  • Page 56: Menu Structure

    BM-2 programming unit 25.2 Menu structure Displays depend on the available extension modules and appliances. Only those menu items are shown that are relevant to the system concerned. Heating Heating Mixer 1 Any other Message appliance circuit displays Operating Operating Fault Operating mode Operating mode message mode mode DHW set temp Set value corr. HP status Set value corr. DHW actual Status Boiler temp. temp Status Room temp.
  • Page 57: Display

    BM-2 programming unit 25.3 Display In the BM-2 "Display" submenu, the following real-time statuses and measured values, as well as statistical system data, can be retrieved. Values are displayed according to system type and configuration. Designation Unit Meaning Heating Boiler water temperature °C Flow temperature (set/actual value) appliance 1 [set/actual] Header temperature [set/actual] °C Header/separating/buffer cylinder temp.
  • Page 58: Standard Settings

    BM-2 programming unit 25.4 Standard settings In the "Standard settings" submenu of the BM-2, the following standard system settings can be configured. Designation Setting range Factory setting Heating appliance Active cooling OFF, ON Night mode → BM FW2.30 → OFF, ON contractor parameter WP066 DHW quick heat-up OFF, ON DHW operating mode ECO, Comfort Heating circuit, mixer 1, ... Economy factor 0.0 ... 10.0 Winter-summer changeover 0.0 ...
  • Page 59: Day Temperature

    BM-2 programming unit When the compressor's application limit is reached (FL/RTN > max.), the electric heater/additional heat generator continues the heating process until the set DHW temperature is reached. If the maximum cylinder heating time is exceeded, DHW mode is interrupted for the duration of the set maximum cylinder heating time (WP022).
  • Page 60: Operating Mode / Hp Status

    Operating mode / HP status 26 Operating mode / HP status 26.1 Operating mode Display Meaning ODU test ODU test Test Relay test active (IDU) Frost prot htg Heat pump frost protection function, heating circuit temperature below frost protection limit (T_boiler, T_return, T_header) Frost prot DHW Heat pump frost protection function, DHW cylinder temperature below frost protection limit DFL low Blocking of heat pump/electric heating until the flow rate is back within valid limits Defrost mode...
  • Page 61: Contractor Level

    Contractor level 27 Contractor level 27.1 AM menu structure, contractor level Main menu Back Displays Standard settings Contractor Back Contractor Contractor code System Relay test 1111 Back Back Back Relay test Enable Heating circuit flow rate System Parallel mode Back Parameter 3way DV HTG/DHW Parameter reset 3way DV HTG/Coolg Special IDU service Electric heater Back ODU service...
  • Page 62: Menu Structure, Contractor Level

    Contractor level 27.2 BM-2 menu structure, contractor level Main menu Display Standard settings Time program Contractor Contractor System Contractor code Heating circuit 1111 System parameters Heating curve (Axx) System Screed drying (see BM-2 installation ● Heating appliance 1-4 instructions) ● Heating circuit ● Mixer 1-7 Solar Heating appliance 1 (heat pump) Cooling curve Mixer / mixers 2-7 Full parameter list Heating curve...
  • Page 63: Description

    Contractor level 27.3 Description (Selection and more details in the AM display module/BM-2 programming unit installation instructions.) 27.3.1 System In the "System" submenu, the contractor can make advanced system settings using system parameters (see AM display module/BM-2 programming unit instructions). 27.3.2 Parameters / full parameter list In the "Heating appliance"...
  • Page 64: Relay Test

    Contractor level 27.3.4 Relay test The "Heating appliance" / "Relay test" submenu allows various outputs or actuators to be manually actuated. On exiting this submenu, the original states, i.e., the states before the "Heating appliance" / "Relay test" submenu was called up, are restored. The various outputs and actuators are displayed according to system type and configuration.
  • Page 65: Odu Service

    Contractor level 27.3.7 ODU service AM display module functions to display a selection of outdoor module (ODU) system data. Designation Unit Meaning Appliance Current appliance output demand output Comp. freq. Compressor speed (rps) Fan speed Fan speed (rpm) T_evap. °C Evaporator temperature T_hot gas °C Hot gas temperature...
  • Page 66: Contractor Parameters

    Contractor parameters 28 Contractor parameters 28.1 Overview Contractor BM-2 designation AM designation Setting range Factory Parameter setting System WP001 System config. System configuration 01, 02, 05, 11, 12, 14, 15, 33, 34, 51, 52 WP002 Function E1 Function input E1 None None RT/DHW Zirkomat DPM / MaxTh WP003 Function A1 Function output A1...
  • Page 67 Contractor parameters Contractor BM-2 designation AM designation Setting range Factory Parameter setting WP033 Cooling with PV/SG Cooling with PV/SG OFF, ON Active cooling WP053 T_outs. enable Coolg Outside temp. to enable cooling 15.0 ... 40.0 °C 25.0 °C WP054 Min flow t cooling Min. flow temp. for cooling 5.0 ... 25.0 °C 20.0 °C WP055 Offset set flow Coolg...
  • Page 68: Contractor Parameters Description

    Contractor parameters 28.2 Contractor parameters description Contractor Description parameter WP001 For setting a pre-configured system version subject to heat pump design and application (see "Overview of system configurations"). WP002 For optionally assigning one of the following functions to programmable input E1: Setting Function input E1 None No function Heating block (room thermostat) Contact open - blocked Contact closed - heating mode enabled DHW block Contact open - blocked Contact closed - DHW mode enabled...
  • Page 69 Contractor parameters Contractor Description parameter WP010 WP016 = ON: For setting the set spread between the flow and return temperatures (heating mode). WP016 = OFF: For setting the offset for the deactivation point in heating mode. For this, the temperatures at the return sensor and the header sensor are monitored. Heat pump OFF: T_return / T_header >...
  • Page 70 Contractor parameters Contractor Description parameter WP058 Enable function for active cooling. WP061 Sets night mode end time (WP061 must be less than WP062) WP062 Sets night mode start time (WP061 must be less than WP062) WP064 Limits maximum possible compressor frequency and fan speed during night mode. WP066 Night mode Used to enable/disable limitation of the maximum possible fan speed and compressor frequency...
  • Page 71: System Configurations

    DHW heating, active cooling possible ON/OFF activation for external demand (e.g. by building management system (BMS)), central heating, DHW heating The entire system must be restarted (power off/power on) each time a change is made to the configuration. Note: Hydraulic diagrams and electrical details can be found on the WOLF homepage and in the "Hydraulic System Solutions" technical guide. QR code for hydraulic database 3064298_201805...
  • Page 72: System Configuration 01

    System configurations 29.2.1 System configuration 01 BWL-1S(B) ● Split air/water heat pump ● Cylinder in series ● One heating circuit ● DHW heating ● Active cooling possible (in conj. with additional 3-way diverter valve for cooling) Heating circuit DHW cylinder Cylinder in series Indoor module Outdoor module 3-way diverter valve heating/cooling (with active cooling) A 3-way diverter valve for central heating/DHW and a feed/heating circuit pump are integrated into the indoor module Important information: In this schematic diagram, shut-off valves, air vent valves and safety equipment are not fully represented.
  • Page 73: System Configuration 02

    System configurations 29.2.2 System configuration 02 BWL-1S(B) ● Split air/water heat pump ● Cylinder in series ● Circuit with mixer extension with MM ● DHW heating ● Solar DHW cylinder ● Solar circuit extension with SM1/SM2 Extension options Circuit with mixer MaxTh Solar circuit Solar DHW cylinder Cylinder in series Outdoor module Indoor module A 3-way diverter valve for central heating/DHW and a feed/heating circuit pump are integrated into the indoor module Important information:...
  • Page 74: System Configuration 05

    System configurations 29.2.3 System configuration 05 BWL-1S(B) ● Split air/water heat pump ● Cylinder in series ● One heating circuit ● DHW heating ● Solar DHW cylinder ● Solar circuit extension with SM1 ● Active cooling possible Important information: In this schematic diagram, shut-off valves, air vent valves and safety equipment are not fully represented. These should be provided for each system individually, in line with the applicable standards and regulations. Hydraulic and electrical data can be found in the hydraulic system solutions technical guide.
  • Page 75: System Configuration 11

    System configurations 29.2.4 System configuration 11 BWL-1S(B) ● Split air/water heat pump ● Separating cylinder ● One heating circuit ● DHW heating Heating circuit DHW cylinder Separating cylinder Please note: Header temperature sensor SAF must be installed in the return area of the low loss Indoor module header or separating cylinder. Outdoor module A 3-way diverter valve for central heating/DHW and a feed/heating circuit pump are integrated into the...
  • Page 76: System Configuration 12 (Bsp-W)

    System configurations 29.2.5 System configuration 12 (BSP-W) BWL-1S(B) ● Split air/water heat pump ● BSP-W ● Solid fuel boiler ● Circuit with mixer extension with MM ● Solar circuit extension with SM1/SM2 ● DHW heating Important information: In this schematic diagram, shut-off valves, air vent valves and safety equipment are not fully represented. These should be provided for each system individually, in line with the applicable standards and regulations. Hydraulic and electrical data can be found in the hydraulic system solutions technical guide.
  • Page 77: System Configuration 12 (Bsh-800/1000)

    System configurations 29.2.6 System configuration 12 (BSH-800/1000) BWL-1S(B) ● Split air/water heat pump ● BSH-800/1000 ● Solid fuel boiler ● Circuit with mixer extension with MM ● Solar circuit extension with SM1/SM2 ● DHW heating Important information: In this schematic diagram, shut-off valves, air vent valves and safety equipment are not fully represented. These should be provided for each system individually, in line with the applicable standards and regulations. Hydraulic and electrical data can be found in the hydraulic system solutions technical guide.
  • Page 78: System Configuration 14

    System configurations 29.2.7 System configuration 14 BWL-1S(B) ● Split air/water heat pump ● BSP-W ● Solid fuel boiler ● Circuit with mixer extension with MM ● Solar circuit extension with SM1/SM2 ● DHW heating ● Active cooling possible 3-way diverter valve heating/cooling 3-way diverter valve heating/cooling Important information: In this schematic diagram, shut-off valves, air vent valves and safety equipment are not fully represented. These should be provided for each system individually, in line with the applicable standards and regulations. Hydraulic and electrical data can be found in the hydraulic system solutions technical guide.
  • Page 79: System Configuration 15

    System configurations 29.2.8 System configuration 15 BWL-1S(B) ● Split air/water heat pump ● Separating cylinder ● Solar DHW cylinder ● Heating circuit ● Circuit with mixer extension with MM ● Solar circuit extension with SM1/SM2 ● DHW heating ● Active cooling possible 3-way diverter valve 3way DV HTG/ heating/cooling Cooling Important information: In this schematic diagram, shut-off valves, air vent valves and safety equipment are not fully represented. These should be provided for each system individually, in line with the applicable standards and regulations. Hydraulic and electrical data can be found in the hydraulic system solutions technical guide.
  • Page 80: System Configuration 33

    System configurations 29.2.9 System configuration 33 3-way diverter valve heating/cooling 3064298_201805...
  • Page 81: System Configuration 34

    System configurations 29.2.10 System configuration 34 BWL-1S(B) ● Split air/water heat pump ● BSH-800/1000 ● TOB (activation via output A1) ● Circuit with mixer extension with MM ● Solar circuit extension with SM1/SM2 ● DHW heating ● Alternatively, dual mode operation only is possible Important information: In this schematic diagram, shut-off valves, air vent valves and safety equipment are not fully represented. These should be provided for each system individually, in line with the applicable standards and regulations. Hydraulic and electrical data can be found in the hydraulic system solutions technical guide.
  • Page 82: System Configuration 51

    System configurations 29.2.11 System configuration 51 External demand / control by U = 0…10 V at input E2/SAF: building management system (BMS) 0 V ≤ U < 1.2 V → heat pump OFF 1.2 V ≤ U ≤ 4.0 V → 0-100 % compressor cooling mode (1...12 % → 12 %) (13...100 % →13...100 %) 4.2 V ≤ U ≤ 7.0 V → 0-100 % compressor heating mode (1...12 % → 12 %) (13...100 % →13...100 %) 7.2 V ≤ U ≤ 10.0 V → 100 % compressor heating mode + 0-100 % elec.
  • Page 83: System Configuration 52

    System configurations 29.2.12 System configuration 52 External demand / control by External floating contact at input E2/SAF: building management system (BMS) Open → heat pump OFF Closed → compressor ON Notes: Application limits: Compressor T_FL/T_RTN = 55 °C, elec. heater T_FL = 75 °C The electric heater is not activated (except for frost protection and defrosting) C onfigure output A1 to defrost (WP003 = Defrost) →...
  • Page 84: Additional Functions

    Additional functions 30 Additional functions 30.1 Active cooling The split air/water heat pump can, in addition to heating/DHW mode, also work in active cooling mode. During active cooling, the cooling capacity of the heat pump is transferred to the heating system. The following conditions must exist for active cooling: System structure in accordance with hydraulic diagram with active cooling option System configuration with active cooling option (WP001 = 01, 05, 14, 15, 51) E1 input function (WP002) = DPM/MaxTh Dew point monitor (DPM) or jumper connected to input E1...
  • Page 85: Pv Increase

    Additional functions 30.3 PV increase The PV increase function enables an adjustment in heat pump operation, e.g. when connected to a photovoltaic (PV) system to optimise on-site consumption of PV energy. An external switching command (floating contact on terminal X1 – 11/12) can increase the set temperature for heating and/or DHW, or enable the active cooling function. The heat pump can be operated using a compressor, electric heater, or both a compressor and electric heater. When configuring on-site technical devices (e.g. PV inverter), take the maximum possible power consumption of the heat pump into account (see specification).
  • Page 86: Smart Grid (Sg)

    Additional functions 30.4 Smart Grid (SG) The Smart Grid (SG) function allows the power supply utility (PSU) to optimally adjust grid utilisation through intelligent control of consumers. Using external switching commands (floating contacts SG_0 and SG_1 on terminals X1 – 9/10 and X1 – 11/12), the compressor and/or electric heater operation can be blocked, or requested with/without an increase in the set heating/ DHW temperatures, or the active cooling function enabled.
  • Page 87: Calculating Set Temperatures When Raising The Temperature Via Pv Or Smart Grid

    Additional functions 30.5 Calculating set temperatures when raising the temperature via PV or Smart Grid. With start recommendation: Set heating temperature = set boiler water temperature Set DHW temperature (max. 64 °C) = set DHW temperature Set cooling temperature = MAX (WP054; (outside temperature – WP055) OR (set boiler water temperature according to cooling curve)) With start command: Set heating temperature = set boiler water temperature + WP026 Set DHW temperature (max.
  • Page 88: Sound Level

    Sound level 31 Sound level Noise levels must be taken into consideration when siting the system. In accordance with TA-Lärm [or local regulations], the following emission limits must be observed: Area Noise emission limits [dB(A)] Night 06:00 - 22:00 22:00 - 06:00 Spa complexes, hospitals and care homes, where indicated as such by means of signs on the premises or road.
  • Page 89: Sound Pressure Level L

    Sound level Q = 4: Heat pump or air intake/discharge (indoor installation) on a house wall Q = 8: Heat pump or air intake/discharge (indoor installation) on a house wall with recessed corner in exterior wall 31.3 S ound pressure level L calculation based on sound power level, distance and directivity Sound power level L dB(A)
  • Page 90: Configuring The Dual Mode Point

    Configuring the dual mode point 32 Configuring the dual mode point 32.1 Configuration example Central heating demand (building heat load) to DIN 4701 or EN 12831 of 7.7 kW. A DHW demand for 4 people (0.25 kW/person) and a standard outside temperature of -16 °C are assumed. The power supply utility specifies a blocking time of 2 x 2 hours. The blocking time factor Z is 1.1. Using these figures, the required heat pump output is calculated as follows: = (Q ) x Z (7.7 kW + 1.0 kW) x 1.1 = 9.6 kW...
  • Page 91: Heating Output, Power Consumption, Cop

    Heating output, power consumption, COP 33 Heating output, power consumption, COP 3064298_201805...
  • Page 92 Heating output, power consumption, COP 3064298_201805...
  • Page 93 Heating output, power consumption, COP 3064298_201805...
  • Page 94 Heating output, power consumption, COP 3064298_201805...
  • Page 95 Heating output, power consumption, COP 3064298_201805...
  • Page 96 Heating output, power consumption, COP 3064298_201805...
  • Page 97 Heating output, power consumption, COP 3064298_201805...
  • Page 98: Heating Circuit Residual Head

    Heating circuit residual head 34 Heating circuit residual head 34.1 Heating circuit residual head BWL-1S(B)-14/16 BWL-1S(B)-10 BWL-1S(B)-05/07 Flow rate [l/min] 34.2 Residual head / nominal water flow rate BWL-1S(B)-05 BWL-1S(B)-07 BWL-1S(B)-10 BWL-1S(B)-14 BWL-1S(B)-16 230 V 230 V 400 V 400 V 400 V Nominal water l/min 15.2 19.7 28.8 34.1 40.2 flow rate Residual head mbar BWL-1S(B)-10 / BWL-1S(B)-14 / 230 V...
  • Page 99: Specification

    Specification 35 Specification TYPE BWL-1S(B) - 05/230 V BWL-1S(B) - 07/230 V Width x height x depth of outdoor unit 964 x 862 x 363 (incl. feet and front doors) Width x height x depth of indoor unit 440 x 790 x 340 (incl. feet and front doors) Weight of outdoor/indoor unit 66 / 33 Refrigerant circuit...
  • Page 100 Specification BWL-1S(B) - BWL-1S(B) - BWL-1S(B) - TYPE 10/400 V 14/400 V 16/400 V Width x height x depth of outdoor unit 964 x 1261 x 363 (incl. feet and front doors) Width x height x depth of indoor unit 440 x 790 x 340 (incl.
  • Page 101 Specification TYPE BWL-1S(B) - 10/230 V BWL-1S(B) - 14/230 V Width x height x depth of outdoor unit 964 x 1261 x 363 (incl. feet and front doors) Width x height x depth of indoor unit 440 x 790 x 340 (incl. feet and front doors) Weight of outdoor/indoor unit 110 / 33 110 / 35...
  • Page 102: Commissioning

    Commissioning 36 Commissioning To ensure correct operation, we recommend that the system is commissioned by our customer service department. A commissioning report with checklist is supplied with every appliance and should be worked through before commissioning. The key criteria are: - Has the appliance been positioned and installed in line with the installation and operating instructions? - Have all electrical and hydraulic connections been completed in full and have you checked that the fan in the outdoor unit can run freely? - Are all slides and shut-off valves in the heating water circuit open?
  • Page 103: System Log Book

    31/12/2016. From 01/01/2017, these systems will then be required to undergo an annual tightness test. WOLF split heat pumps use F-gas R410A, an HFC mixture with a global warming potential (GWP100) of 2088. This means that 1 kg of R410A equates to 2.088 t of CO2.
  • Page 104: Compulsory Documentation

    System log book 37.1.2 Compulsory documentation All work carried out on a heat pump, e.g. maintenance, repair and tightness tests, must be documented and the record of results must be retained for five years. This obligation applies to the operator and the company carrying out the work. The following data must be entered: f Details of all repair and maintenance work f Type of refrigerant filled into the system (new, re-used or recycled)
  • Page 105: The Following System Data Must Be Documented

    Postal address _____________________________________________________________ Installation location _____________________________________________________________ Tel. no. of system operator WOLF heat pump type: _________________________________________ Outdoor unit serial number _______________________________________ Year of construction ____________________________________________ Commissioning ________________________________________________ Refrigerant/charge weight _______________________________________ The above data can be found on the type plate of the appliance.
  • Page 106 System log book The following maintenance work and regulatory tightness tests (to para 5, section 3 of the ChemKlimaschutzV (chemicals climate protection ordinance) in conjunction with EC Regulation No. 303/2008 - Category I) have been carried out on the heat pump's refrigerant circuit: Date - Results of maintenance Name of specialist...
  • Page 107: Maintenance / Cleaning

    Maintenance / cleaning 38 Maintenance / cleaning Although heat pumps are considered low-maintenance heating systems, regular periodic maintenance work offers advantages. • Operational reliability is maintained. • A consistently high seasonal performance factor is achieved. • Low fault rate. • The service life of system components can be prolonged. •...
  • Page 108: Cleaning The Evaporator On The Bwl-1S(B)

    Maintenance / cleaning 38.2 Cleaning the evaporator on the BWL-1S(B) In areas with high concentrations of dust or pollen, shorter cleaning intervals may be necessary Please alongside the mandatory annual inspection and cleaning, in order to ensure that the system note operates efficiently. Adjust the cleaning interval to suit the local conditions. The evaporator must be checked annually for dirt/contamination and cleaned if necessary. Wet cleaning with a commercially available garden hose is recommended. Contaminated fins may reduce the system's transfer performance and consequently its energy efficiency, and in the worst case scenario may result in system failure. When cleaning, ideally use a wide nozzle with a spray angle of 15° - 20°. To prevent damage to the fins, direct the water spray at the evaporator surface from the front at an angle of 90°.
  • Page 109: Troubleshooting

    Any faults or damage which impact or might impact upon safety must be remedied immediately by a qualified contractor. Replace faulty components and equipment only with original WOLF spare parts. Faults are shown in plain text on the display of the control accessory – AM display module or BM-2 programming unit –...
  • Page 110: Fault Codes

    Troubleshooting 39.5 Fault codes Fault Short designation Possible cause Remedy code Boiler sensor faulty Flow temperature (T_boiler) outside Check flow temperature (T_boiler) permissible range (0 … 95 °C) Lead to sensor is faulty Check lead and plug-in connection Sensor faulty Check/replace sensor DHW sensor faulty DHW cylinder temperature outside Check DHW cylinder temperature...
  • Page 111 Troubleshooting Fault Short designation Possible cause Remedy code T_intake gas Refrigerant temperature outside permissible Check lead and plug-in connection (AWO) range Check refrigerant temperature Lead to sensor is faulty Check/replace sensor Sensor faulty (condenser temperature (IRT)) T_hot gas Hot gas temperature outside the permissible Contact service engineer range (ODU, CTT sensor) T_supply air...
  • Page 112: Technical Parameters To Eu Regulation No. 813/2013

    Nominal water or brine flow rate Contact WOLF GmbH, Industriestrasse 1, 84048 Mainburg, Germany (*) For heating appliances and combi boilers with heat pump, the rated heating output P is equal to the design load in heating mode P...
  • Page 113 Outdoor sound power level For air/water heat pump: Nominal m3/h 3800 3800 3800 3800 air flow rate, outdoors For water/brine-water heat pump: m3/h Nominal water or brine flow rate Contact WOLF GmbH, Industriestrasse 1, 84048 Mainburg, Germany 3021351 06/2017 3064298_201805...
  • Page 114: Product Datasheet To Eu Regulation No. 811/2013

    4,287 6,120 6,848 te conditions Annual energy consumption under warmer cli- 1,345 1,687 2,119 2,956 mate conditions Sound power level, outdoors Wolf GmbH, Postfach 1380, D-84048 Mainburg, Tel. +49-8751/74-0, Fax +49-8751/741600, Internet: www.wolf-heiztechnik.de Material number: 3021352 08/2017 3021351 06/2017 3064298_201805...
  • Page 115 6,120 6,848 10,803 te conditions Annual energy consumption under warmer cli- 2,119 3,061 2,959 1,896 mate conditions Sound power level, outdoors Wolf GmbH, Postfach 1380, D-84048 Mainburg, Tel. +49-8751/74-0, Fax +49-8751/741600, Internet: www.wolf-heiztechnik.de Material number: 3021352 08/2017 3021351 06/2017 3064298_201805...
  • Page 116 Annual energy consumption under colder clima- 4446 5213 9125 7439 te conditions Annual energy consumption under warmer cli- 1906 2717 2862 3765 mate conditions Sound power level, outdoors Wolf GmbH, Postfach 1380, D-84048 Mainburg, Tel. +49-8751/74-0, Fax +49-8751/741600, Internet: www.wolf-heiztechnik.de Material number: 3020915 08/2017 3064298_201805...
  • Page 117 Annual energy consumption under colder clima- 9125 7439 9032 te conditions Annual energy consumption under warmer cli- 2862 5083 3765 3924 mate conditions Sound power level, outdoors Wolf GmbH, Postfach 1380, D-84048 Mainburg, Tel. +49-8751/74-0, Fax +49-8751/741600, Internet: www.wolf-heiztechnik.de Material number: 3020915 08/2017 3064298_201805...
  • Page 118: Abbreviations / Key

    Abbreviations / key Abbreviations / key 0-10 V/On-Off - Input for external demand 3way DV HTG/Coolg - 3-way diverter valve for heating/cooling 3way DV HTG/DHW - 3-way diverter valve for heating/DHW A1 - Programmable output 1 AF - Outside temperature sensor AM - Display module AWO - AWO board (= communication board in indoor module) BCC - Appliance type connector (GTS) BM-2 - Programming unit-2...
  • Page 119: Notes

    Notes 43 Notes 3064298_201805...
  • Page 120 DECLARATION OF CONFORMITY (to DIN EN ISO/DIN 17050-1) Number: 3064298 Issuer: WOLF GmbH Address: Industriestrasse 1, 84048 Mainburg, Germany Product: Split air/water heat pump BWL-1S -05/230 V BWL-1SB - 05/230 V BWL-1S -07/230 V BWL-1SB - 07/230 V BWL-1S -10/400 V BWL-1SB - 10/400 V BWL-1S -14/400 V BWL-1SB - 14/400 V...

Table of Contents

Save PDF