Height differentials
Cooling mode
Injection line
(phase mixture)
Liquid line (liquid)
24

15. Routing the refrigerant lines

The outdoor module is pre-filled with refrigerant R410A.
No additional filling is required for lines up to 12 m in length.
Minimum line length
Maximum line length
Max. height differential
Indoor to outdoor unit
Line lengths between 12 and 25 m must be topped up with an additional 60 g/m
refrigerant R410A.
If the height differential between the indoor and the outdoor units is > 4 m,
both refrigerant lines will require oil riser elbows to prevent oil shortages in the
compressor.
Outdoor module higher than indoor module
Suction line
Oil lift bend
(gaseous)
Max. 4 m
Indoor module higher than outdoor module
Heating mode
Hot gas line
(gaseous)
Max. 4 m
: 3 m
: 25 m
: 15 m
(on site)
Liquid line (liquid)
Oil lift bend
(on site)
Heating mode
Hot gas line
(gaseous)
Max. 4 m
Cooling
mode
Injection line
Suction line
(phase mixture)
(gaseous)
Max. 4 m
3064298_201507