Wolf BWL-1 S Installation And Operating Instructions Manual page 41

Split air/water heat pump
Table of Contents

Advertisement

230 V mains connection
The control and safety equipment is fully wired and tested.
You only need to connect the power supply and the external
accessories.
Create a permanent connection for the power supply.
Provide the power supply via a mains isolator (e.g. heating
system emergency stop switch) that ensures at least 3 mm
contact separation for all poles.
No other consumers may be connected to the connection
cable. In rooms with a bathtub or shower, the appliance may
only be connected via an RCD.
The mains supply to the indoor module must be without power-
OFF facility and switchable tariffs.
Note:
During power-OFF, it is not possible to operate the compressor
with power generated on site (PV temperature raising).
Installation information / Electrical connection
- Isolate the system from the power supply before opening.
- Remove front casing.
- Open the control unit cover.
- Check that the appliance is isolated from the power supply.
- Push the cable through the cable entry.
- Pull off Rast5 plug.
- Terminate the appropriate cores at the Rast5 plug.
Connection, output Z1 (230 V AC; max. 1.5 A) *
Push connecting cable through cable entry. Connect the
connecting cable to terminals L1, N and
* M ax. 1.5 A / 345 VA per output, sum of all outputs no more
than 600 VA
3064298_201507
25. Power supply to the indoor module
.
3
Fig: Mains connection
3
Fig: Output Z1 connection
41