Specifications - Toshiba UE3G2L036C61T Instruction Manual

Uninterruptible power system single phase – 3.6/ 6/8/10 /14/18 kva /1600ep series
Hide thumbs Also See for UE3G2L036C61T:
Table of Contents

Advertisement

UPS Specifications
Capacity
General
Topology
Certifications
Input Characteristics
Input Voltage
Input Frequency
Input Capacity
Input Power Factor
Current THD (linear load)
Battery Characteristics
Battery Type
Backup time, fully charged
@ 0.7 power factor, 77 F
Backup time, fully charged
@ 0.85 power factor, 77 F
Recharge Time
Battery Voltage (Nominal)
Output Characteristics
Output Voltage
Output Voltage Regulation
Output Frequency
AUTO/MAN Frequency
Voltage THD
Common-Mode Noise
Rated Load Power Factor
Efficiency (ac-dc-ac)
Voltage Transient
Rated Output Current (rms)
Max. Peak Output Current
Inverter Overload Capacity
Bypass Overload Capacity
Crest Factor
Environment
Operating Temperature
(15 ~ 25° C recommended)
Storage Temperature
Installation Area
Operating Humidity
Altitude
Acoustical Noise
Operation Diagnosis
Battery Check
Input OV Protection
Battery Lifetime
Internal Temperature
TOSHIBA
STANDARD MODELS
3.6kVA (3.1kW)*
True On-line
UL, CUL, ISO 9001, NEMA/PE1-1993
Single-phase, 208/240 Vac, +10% to –30%*
45-65 Hz (auto-sensing)
3.6kVA
> 0.95 for all loads
< 5%
Valve Regulated Lead Acid, Flame Retardant
3.6kVA
14 minutes
7 minutes minimum**
minimum**
10 minutes
7 minutes minimum**
minimum**
24hr. (full), 12hr.(90%) for internal batteries only***
216Vdc
Single-phase, 240/208/120 volts
+/- 3%
+/-0.5Hz/1Hz/1.5Hz (factory or authorized service center selectable only)
Factory or authorized service center selectable only
< 3% for linear load; < 6% for non-linear load
< .5Vrms
0.85 (0.6 - 1.0) lagging
> than 83% (without battery charge)
< +/-8% (Load of 0 to 100 %)
15.0A
45.0A
125%-30sec/150%-10sec
125%-10min./1000%-1 cycle
3.0
60Hz
0 ~ 40° C
-20 ~ 40° C (-4 to 104° F)
To be installed in a well ventilated area free of airborne dust, metal
particles or flammable gas, allow at least 4 inches on all sides
30 ~ 90%(no condensation)
< 1000m above sea level****
50 dB (A) maximum @ 1 meter from front panel
Performed on start up, by schedule, on-demand (user configurable)
Standard
UPS calculates battery replacement time based upon battery ambient
temperature (LCD display, LED and beeps)
UPS gives indication of internal temperature, alarm when high temp
18
6kVA (5.1kW)*
8kVA (6.8kW)*
6kVA
6kVA
7 minutes minimum**
7 minutes minimum**
216Vdc
25.0A
75.0A
50Hz
0 ~ 33° C
8kVA
8kVA
288Vdc
33.3A
100.0A