Display Screens

UPS Start-up Screens

The LCD will automatically display the basic system start-up functions when AC input power is
turned on to the unit (see "Starting the UPS on page 41). The basic start-up function
indicates the operating state of the unit. If the correct ac input power is available and
no abnormal operating conditions are present then the following system message will be
displayed on the LCD screen:
TOSHIBA 1600 UPS
INITIALIZING...
The LCD will automatically and sequentially display the date function on the first line and the
time function on the second line. The following screen is an example. The correct date and
time can be set (see Date Time function setting on page 32):
11/04/2001(WED)
15:22:47
The LCD will automatically and sequentially display on the first line that the UPS is in bypass operation
mode and the second line will display the percentages of maximum load that are connected. The
value shown is the percentage loaded. This screen will continue to be displayed until the key
is pressed unless the automatic operation (see 'auto run' page 32) is set to "Y". If the connected loads
are varied then the load percentages will change. The UPS inverter is not "on" and running then if the
AC input power is removed from the unit the output will stop:
BYPASS OPERATION
LOAD ###%
The UPS operation starts immediately when the
operation is set to turn it on (see 'auto run' data setting screen on page 32). The LCD will automatically
display on the first line that the UPS is in the normal operation mode and the second line will display
the percentages of maximum load that is connected. The value is the percentage loaded:
UPS OPERATION
LOAD ###%
The UPS internal batteries are automatically tested and the following screen appears while the
testing is being done. The first line indicates that a battery test is occurring. The second line
indicates the present battery voltage level as a percentage of full charge:
BATTERY TEST
BAT VOLTAGE ##%
The LCD will automatically and sequentially display on the first line that the UPS is in normal
operation mode. The second line will display the percentages of maximum load that are
connected. The value is the percentage loaded.
UPS OPERATION
LOAD ###%
TOSHIBA
Note: If input voltage is removed
while UPS is in the Bypass
Mode then the output stops.