IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS
be followed during the installation and maintenance of the UPS and its batteries.
Hardwire type UPS units are not equipped with an over-current protection device nor an output
disconnect for the ac output. Therefore, a circuit breaker should be provided by the user between the
UPS output and the load input. This device should be rated as follows:
240VAC
3.6kVA
RATING
20A
The maximum ambient temperature in which the UPS unit should be operated in is 104° F (40° C).
The nominal battery voltages for these models are as follows:
3.6kVA
BATTERY
VOLTAGE
216Vdc
Servicing of the batteries should only be performed by a qualified Toshiba Representative who is
knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from
batteries. To arrange for battery replacement, contact your nearest Toshiba authorized service
center.
CAUTION
CAUTION
CAUTION
TOSHIBA
6kVA
8kVA
30A
40A
6kVA
8kVA
216Vdc
288Vdc
Misuse of this equipment could result in human injury and equipment
damage. In no event will Toshiba Corporation be responsible or liable for
either indirect or consequential damage or injury that may result from the
use of this equipment.
Do not dispose of the batteries in a fire. The batteries may explode.
Do not open or mutilate the batteries. Released electrolyte is harmful to
the eyes and skin and could also be toxic.
This manual contains important instructions
for 3.6, 6, 8, 10, 14, and 18 kVA that should
10kVA
14kVA
60A
80A
10kVA
14kVA
288Vdc
288Vdc
8
18kVA
125A
18kVA
288Vdc