5.1 Operation Modes

Online Mode
z
z
During online mode, the ONLINE LED (green) and the LOAD LED (green) il-
luminate. If loads are connected to the UPS, the Bar Graph LEDs (green) will
illuminate or flash to indicate the occupied rated capacity (%). For information
about the Bar Graph LEDs, please refer to 2.4 Front Panel. In online mode, the
connected loads are supplied by the utility AC power, and the UPS charges the
batteries as needed and provides power protection to the connected loads from
a variety of power line problems.
Battery Mode
z
z
When the UPS is operating during a power outage, the batteries provide DC
power, which maintains inverter operation to support the loads. During battery
mode, the ON BATT. LED (green) and the BATT. LED (green) illuminate, and
the Bar Graph LEDs (green) illuminate or flash to indicate the reaming battery
capacity. For information about the Bar Graph LEDs, please refer to 2.4 Front
Panel. You can use the UPSentry 2012 software (included in the provided CD),
SNMP card (optional), or ModBus card (optional) to monitor and estimate the
battery remaining capacity before or during an AC power failure. For more infor-
mation about the SNMP card (optional) or the ModBus card (optional), please
refer to its user manual.

5.2 Other Operating Details

1. Please refer to 2.4 Front Panel, 2.5 Rear Panel and Chapter 6 : Communica-
tion Interfaces to understand how to use the UPS interfaces.
2. Cold Start : The UPS is able to start up via battery source when there is no AC
power available.
3. Site Wiring Fault Detection : The unit can detect if input line and input neutral
have been inverted. If yes, the S.W.F LED on the front panel will illuminate (red).
4. Battery Test : The UPS can perform battery test manually upon user request
or automatically. For automatic regular test, please install the UPSentry 2012
software (included in the provided CD), or configure the SNMP card (optional)