Technician Level

The Technician level allows complete programming of the MPC-6000/MPC-7000/RND-
2. See the User level functions for the method to access the Technician level. The steps
below assume that the Technician level has been accessed and that the panel is
displaying the starting screen of the Technician level.

Activating the Releasing Application Features

During initial power-up, the releasing application features are defaulted to NOT
INSTALLED state and need to be activated to use the panel for releasing application.
When this feature is activated, it allows the user to select releasing application features
at various levels of programming.
Action
1. From Tech Level Screen, select "Edit".
2. Select "Manual Pgm".
3. Select "Cmor," then select "Sys Params."
4. Select "Cmor" three times then select
"Releasing."
5. Press Bsav to save the selection.

Configuring the Releasing Application Features

After the releasing application features have been activated, its parameters need to be
configured.
Action
1. From Tech Level Screen, select "Edit".
2. Select "Manual Program."
3. Select "Cmor," then select "Releasing."
4. After configuring the Releasing Application
Parameters, press Bsav to save the selections.
The following provides a description of the releasing application parameters.
Parameters
Sublevel
Agent Rel
Enter the desired time using the
Delay
numeric keypad in 5 sec.
Increments.
Shutoff
Enter the desired time using the
Period
numeric keypad in 5 sec.
increments.
Abort
ULI
Type
*
IRI
AHJ
NYC
M P C - 6 0 0 0
/
M P C - 7 0 0 0
Result
Enter the Edit Backup Screen.
Enter the Manual Programming Screen.
Enter the System Parameter Programming
Screen.
Enter the Releasing Application Prompt. Select
YES to enable the releasing application feature.
Saves the selection to the Backup program.
Result
Enter the Edit Backup Screen.
Enter the Manual Programming Screen.
Enter the Releasing Parameter Programming
Screen.
Saves the selection to the Backup program.
Description
This parameter sets the time delay before the
releasing circuits activate once the releasing set
thresholds are met. (Default – 30 sec.) Range: 0-
90 seconds.
This parameter sets the time the releasing circuit is
active. This timer starts as soon as releasing circuit
activates. (Default – 60 sec.) Range: 20-60 seconds.
This parameter determines the action of the
panel when the abort switch is initiated while the
system is in Pre-Discharge condition.
ULI - Abort condition is initiated during Pre-
Discharge condition only. Pre-Discharge delay
counts down or restores to 10 sec. then holds if
abort is pressed and resumes countdown if abort
switch is released.
25
/
R N D - 2
P R O G R A M M I N G
M A N U A L