Faraday 15220A Owner's Manual

System control unit

Advertisement

FARADAY
15220A / 15240A
15220A-240/15240A-240
FIRE ALARM
SYSTEM CONTROL UNIT
OWNERS MANUAL
P/N 445926
ISSUE I Rev. C
10/98
805 S. Maumee St. / Tecumseh, MI 49286
FARADAY
Phone: (517) 423-2111 / Fax: (517) 423-2320
Copyright © 1998, Faraday, LLC All Rights Reserved
firealarmresources.com

Advertisement

Table of Contents
loading

Summary of Contents for Faraday 15220A

  • Page 1 15220A-240/15240A-240 FIRE ALARM SYSTEM CONTROL UNIT OWNERS MANUAL P/N 445926 ISSUE I Rev. C 10/98 805 S. Maumee St. / Tecumseh, MI 49286 FARADAY Phone: (517) 423-2111 / Fax: (517) 423-2320 Copyright © 1998, Faraday, LLC All Rights Reserved firealarmresources.com...
  • Page 2 PAGE INSTALLATION AND WARRANTY INFORMATION PREFACE PANEL PERFORMANCE PARAMETERS SECTION I DESCRIPTIONS 15220A/15240A FIRE ALARM SYSTEM CONTROL UNIT 15216 SEMI-FLUSH TRIM 14047 6 A.H. BATTERY SET 14048 10 A.H. BATTERY SET 14049 15 A.H. BATTERY SET 14050 BATTERY CABINET 15212 REMOTE ANNUNCIATOR MODULE...
  • Page 3: Table Of Contents

    SECTION III INSTALLATION INSTRUCTIONS - (CONTINUED) (FOR QUAILFIED PERSONNEL ONLY) PAGE WIRING DIAGRAM FOR SYSTEM SENSOR 4-WIRE DETECTORS III-21 WIRING DIAGRAM FOR SYSTEM SENSOR 4-WIRE DUCT DETECTORS III-22 WIRING DIAGRAM FOR SYSTEM SENSOR 4-WIRE BEAM DETECTORS III-23 COMPATIBLE SIGNALS III-24 WIRING DIAGRAM FOR SIGNAL CIRCUIT III-30 WIRE SELECTION GUIDES...
  • Page 4 DATE INSTALLED:____________________________INSTALLER'S SIGNATURE:___________________________ ORIGINAL PURCHASER INFORMATION COMPANY:_________________________________________________________PHONE:____________________ ADDRESS:__________________________________CITY:__________________STATE:___________ZIP:____________ PURCHASER'S PURCHASE ORDER NO.:___________________________________________________________ DATE PURCHASED:_____________________________________________________________________________ FARADAY SALES ORDER ACKNOWLEDGMENT NO.:_________________________________________________ ORIGINAL PURCHASER'S SIGNATURE:____________________________________________________________ NOTE: A COPY OF THE ABOVE COMPLETED INFORMATION MAY BE REQUIRED BY THE MANUFACTURER FOR AUTHORIZATION OF WARRANTY SERVICES. firealarmresources.com...
  • Page 5 PREFACE Along with the use of this Instruction Manual, the appropriate following standards and the manufacturers' instructions for initiating and signaling devices should be used to install and maintain a functioning Fire Alarm Signaling System. National National Electrical Electrical Code Code 1993 1993...
  • Page 6 PANEL PERFORMANCE PARAMETERS This control panel will not show an alarm condition without compatible initiating devices (smoke detectors, etc.) and indicating devices (horn, lights, etc.) connected to it. Electrical ratings of the initiating and indicating appliances must be U.L. listed compatible with the electrical ratings of the control panel and must be properly interconnected.
  • Page 7 OF A SECONDARY AND TROUBLE SIGNAL POWER SUPPLY. SEE SECTION III FOR CALCULATING BATTERY REQUIREMENTS: The 14047 Battery Set provides 6 Amp.- Hours of capacity @ 24 volts and mounts in the 15220A or 15240A Fire Alarm System Control Unit cabinet.
  • Page 8 The 15217 Auxiliary Relay Module is an optional module for the 15220A or 15240A Fire Alarm System Control Unit. This module provides a form "C" trouble contact and a form "C" general alarm contact. The module also contains a disconnect switch and a trouble / off-normal switch L.E.D. The disconnect switch may be activated during testing or servicing of the system to prevent transferring the general alarm contact (a trouble output will be generated upon activation of the disconnect switch).
  • Page 9 15220A/15240A GENERAL SPECIFICATIONS Normal Operating Ambient Temperature: 68°- 77°F (20°-25°C) Extreme Ambient Temperature: 32°-120°F (0°-49°C) up to 3 hours Extreme Relative Humidity: 85% @ 86°F (30°C) up to 24 hours Primary Input Voltage: 15220A / 15240A 120VAC 50/60Hz Nominal (102-132 VAC)
  • Page 10 firealarmresources.com...
  • Page 11 OWNERS INSTRUCTIONS ALARM OPERATION OF THE FIRE ALARM SYSTEM CONTROL UNIT An alarm is indicated by the following conditions: A red zone ALARM L.E.D. lights. The yellow SYSTEM TROUBLE L.E.D. lights in a pulsating manner. The trouble buzzer sounds in a pulsating manner. The building alarm signals activate.
  • Page 12 OWNERS INSTRUCTIONS (Cont'd) TROUBLE OPERATION OF THE FIRE ALARM SYSTEM CONTROL UNIT A trouble is indicated by the following conditions: The yellow SYSTEM TROUBLE L.E.D. lights in a pulsating manner. The trouble buzzer sounds in a pulsating manner. Depending on the type of trouble, a yellow zone TROUBLE L.E.D. or a yellow trouble L.E.D.
  • Page 13 (Yellow) Indicates, in a pulsating manner, that a trouble condition NOTE: Zones #3 and #4 are not used on the exists in the fire alarm system. 15220A Fire Alarm System Control Unit. Zone Alarm: (Red) Indicates an alarm condition in the associated zone.
  • Page 14 DO NOT LEAVE SWITCHES IN THE DISCONNECTED POSITION! MAINTENANCE The 15220A or 15240A Fire Alarm System Control Unit does not require periodic maintenance except that the unit should be kept clean and dry. Sealed Lead Acid batteries should be replaced every four years or if the voltage is low.
  • Page 15 15220A / 15240A OPERATING INSTRUCTIONS ALARM OPERATION OF THE FIRE ALARM SYSTEM CONTROL UNIT AN ALARM IS INDICATED BY: A RED zone ALARM L.E.D. lights. The YELLOW SYSTEM TROUBLE L.E.D. flashes. The trouble buzzer sounds. Notify the proper personnel to institute preplanned Fire Alarm Procedures:____________________________________________ Telephone the Fire Department.
  • Page 16 CAT NO. 15220A OR 15240A FIRE ALARM CONTROL UNIT The 15220A, Two Zone, and 15240A, Four Zone, Fire Alarm System Control Unit provides manual, automatic, and waterflow alarm and supervisory service. Zone #1, may be used as a manual, auto- matic, or waterflow initiating circuit or it can be programmed to be used with normally open sprinkler supervisory switches.
  • Page 17 Step 3.) Attach conduit (if required) and run wires as Step 2.) B.) Use four #10 lag screws (not supplied) to required. Do not connect wires at this time. secure the control unit to the wall. Non power limited field wires must be run in separate conduit and be 1/4"...
  • Page 18 Step 4.) Reinstall the main board as originally installed. Step 5.) Connect the primary (main) power supply wires to the control unit. Step 6.) Apply power to system. The following indications must occur: A.) System power L.E.D. on. B.) System trouble L.E.D. flashing. C.) Trouble buzzer pulsating.
  • Page 19 Step 8.) D.) If a 14049 battery set is used: 1.) Mount the 14050 battery cabinet. 2.) Place the batteries in the battery cabinet. 3.) Use crimp-on terminals to connect batteries in series with #12 AWG wires 4.) Cut off receptacle provided on the black "B-" lead and connect with #12 AWG wire to the black or "-"...
  • Page 20 Step 14.) If sprinkler supervisory switches are used: A.) Connect normally open switch contacts, in parallel, to Zone #1. B.) Diodes D27, D30 and D31 must be cut out of the main board. NOTE: The L.E.D. indicator mask must be removed to locate the diodes.
  • Page 21 BACKBOX DIMENSIONS III- 6 firealarmresources.com...
  • Page 22 SEMI-FLUSH MOUNTING DIAGRAM III- 7 firealarmresources.com...
  • Page 23 15220A WIRING DIAGRAM FARADAY NOTES: Units to be installed in accordance with the National Electric Code and/or local electric codes. See the Signal Circuit Wire Selection Guide to determine wire size for signal circuits #1 and #2. The 120VAC terminal block will accept up to #12 AWG wiring or .312" spade terminals.
  • Page 24 15220A-240 WIRING DIAGRAM FARADAY NOTES: Units to be installed in accordance with the National Electric Code and/or local electric codes. See the Signal Circuit Wire Selection Guide to determine wire size for signal circuits #1 and #2. The 120VAC terminal block will accept up to #12 AWG wiring or .312" spade terminals.
  • Page 25 This wiring diagram only shows general CIRCUIT information about the initiating device. For specific wiring and installation information read the instructions provided with each device. For initiating circuit specifications see the 15220A Wiring Diagram (445928) or the 15240A Wiring Diagram (445929). III- 10 firealarmresources.com...
  • Page 26 This wiring diagram only shows general CIRCUIT #1 information about the initiating device. For specific wiring and installation information read the instructions provided with each device. For initiating circuit specifications see the 15220A Wiring Diagram (445928) or the 15240A Wiring Diagram (445929). III- 11 firealarmresources.com...
  • Page 27 This wiring diagram only shows general CIRCUIT #2 information about the initiating device. For specific wiring and installation information read the instructions provided with each device. For initiating circuit specifications see the 15220A Wiring Diagram (445928) or the 15240A Wiring Diagram (445929). III- 12 firealarmresources.com...
  • Page 28 (ZONE IDENTIFIER “C”) This list of 2-wire smoke detectors has been approved by U.L. for use with the 15220A and 15240A Fire Alarm System Control Unit. To insure proper operation, no other types of 2-wire smoke detectors should be used.
  • Page 29 U.L. COMPATIBLE 2-WIRE SMOKE DETECTORS (Cont'd) FOR 15220A AND 15240A FIRE ALARM SYSTEM CONTROL UNITS (ZONE IDENTIFIER “C”) DETECTOR MANUFACTURER NUMBER OF MAXIMUM W/BASE DETECTOR DETECTORS STANDBY DETECTOR BASE ORDER NO. W/ BASE PER CIRCUIT CURRENT INENTIFIER IDENTIFIER DETECTION SYSTEMS, INC. (DSI)
  • Page 30 U.L. COMPATIBLE 2-WIRE SMOKE DETECTORS (Cont'd) FOR 15220A AND 15240A FIRE ALARM SYSTEM CONTROL UNITS (ZONE IDENTIFIER “C”) DETECTOR MANUFACTURER NUMBER OF MAXIMUM W/BASE DETECTOR DETECTORS STANDBY DETECTOR BASE ORDER NO. W/ BASE PER CIRCUIT CURRENT INENTIFIER IDENTIFIER HOCHIKI-AMERICA CORP. ALPHA-LARM DIV.
  • Page 31 1.) For specific wiring and installation information read the instructions provided with each device. 2.) For initiating circuit specifications, see the 15220A wiring diagram or 15240A wiring diagram. 3.) These detector models may be mixed and matched as long as total maximum standby current does not exceed 3.0 ma.
  • Page 32 This wiring diagram only shows general information about the initiating device. For specific wiring and installation information read the instructions provided with each device. For initiating circuit specifications see the INITIATING 15220A Wiring Diagram (445928) or the CIRCUIT 15240A Wiring Diagram (445929). III- 17 firealarmresources.com...
  • Page 33 This wiring diagram only shows general information about the initiating device. For specific wiring and installation information read the instructions provided with each device. For initiating circuit specifications see the INITIATING 15220A Wiring Diagram (445928) or the CIRCUIT 15240A Wiring Diagram (445929). III- 18 firealarmresources.com...
  • Page 34 COMPATIBLE 4-WIRE SMOKE DETECTORS FOR 15220A AND 15240A FIRE ALARM CONTROL PANELS Compatible 4-Wire Smoke Detectors must have a minimum absolute voltage range of 19 to 28 V.D.C. DECTECTOR MANUFACTURER MAXIMUM MAXIMUM W/BASE DETECTOR STANDBY ALARM ORDER NO. W/BASE CURRENT...
  • Page 35 COMPATIBLE 4-WIRE SMOKE DETECTORS (Cont'd) FOR 15220A AND 15240A FIRE ALARM CONTROL PANELS Compatible 4-Wire Smoke Detectors must have a minimum absolute voltage range of 19 to 28 V.D.C. DECTECTOR MANUFACTURER MAXIMUM MAXIMUM W/BASE DETECTOR STANDBY ALARM ORDER NO. W/BASE...
  • Page 36 This wiring diagram only shows general information about the initiating device. For specific wiring and installation information read the instructions provided with each device. For initiating circuit specifications see the INITIATING 15220A Wiring Diagram (445928) or the CIRCUIT 15240A Wiring Diagram (445929). III- 21 firealarmresources.com...
  • Page 37 This wiring diagram only shows general information about the initiating device. For specific wiring and installation information INITIATING read the instructions provided with each CIRCUIT device. For initiating circuit specifications see the 15220A Wiring Diagram (445928) or the 15240A Wiring Diagram (445929). III- 22 firealarmresources.com...
  • Page 38 This wiring diagram only shows general information about the initiating device. For specific wiring and installation information read the instructions provided with each device. For initiating circuit specifications see the 15220A Wiring Diagram (445928) or the INITIATING 15240A Wiring Diagram (445929). CIRCUIT III- 23 firealarmresources.com...
  • Page 39: Compatible Signals Iii-24

    COMPATIBLE SIGNALS Audible Audible Strobe Strobe Cat. No. Description Voltage Current Voltage Current 446(*1) Bell - Vibrating 21-30VDC 0.110A. 476(*1) Bell - Vibrating 21-30VDC 0.070A. 477(*1) Bell - Single Stroke 21-30VDC 0.360A. 2700-E Strobe Light 20-31VDC 0.059A. 2700-G Strobe Light 20-31VDC 0.089A.
  • Page 40 COMPATIBLE SIGNALS (cont'd) Audible Audible Strobe Strobe Cat. No. Description Voltage Current Voltage Current 5337-(H,U) Electronic Horn-3T w/ Strobe 21-32VDC 0.020-0.25A.(*4) 21-30VDC 0.075A. 5337-(N,W) Electronic Horn-3T w/ Strobe 21-32VDC 0.020-0.25A.(*4) 21-32VDC 0.079A. 5337-D Electronic Horn-3T w/ Strobe 21-32VDC 0.020-0.25A.(*4) 21-32VDC 0.175A.
  • Page 41 COMPATIBLE SIGNALS (cont'd) Audible Audible Strobe Strobe Cat. No. Description Voltage Current Voltage Current 5386-S Electronic Signal-8T w/ Strobe 12-32VDC 0.020-0.50A.(*4) 21-32VDC 0.245A. 5386-(A,B) (*2) Electronic Signal-8T w/ Sync Strobe 12-32VDC 0.020-0.50A.(*4) 20-31VDC 0.145A. 5386-C (*2) Electronic Signal-8T w/ Sync Strobe 12-32VDC 0.020-0.50A.(*4) 20-31VDC...
  • Page 42 COMPATIBLE SIGNALS (cont'd) Audible Audible Strobe Strobe Cat. No. Description Voltage Current Voltage Current 5519-(N,W) Strobe Light 21-32VDC 0.079A. 5519-D Strobe Light 21-32VDC 0.175A. 5519-S Strobe Light 21-32VDC 0.245A. 5519-(A,B) (*2) Sync Strobe Light 20-31VDC 0.145A. 5519-C (*2) Sync Strobe Light 20-31VDC 0.285A.
  • Page 43 COMPATIBLE SIGNALS (cont'd) Audible Audible Strobe Strobe Cat. No. Description Voltage Current Voltage Current 6235-E WP Horn w/ Strobe 21-30VDC 0.038A. 20-31VDC 0.059A. 6235-L WP Horn w/ Strobe 21-30VDC 0.038A. 20-31VDC 0.249A. 6235-M (*2) WP Horn w/ Sync Strobe 21-30VDC 0.038A.
  • Page 44 COMPATIBLE SIGNALS (cont'd) Audible Audible Strobe Strobe Cat. No. Description Voltage Current Voltage Current 6302-D Mini-Horn w/ Strobe 20-31VDC 0.025A. 21-32VDC 0.175A. 6302-S Mini-Horn w/ Strobe 20-31VDC 0.025A. 21-32VDC 0.245A. 6302-(A,B) (*2) Mini-Horn w/ Sync Strobe 20-31VDC 0.025A. 20-31VDC 0.145 A 6302-C (*2) Mini-Horn w/ Sync Strobe 20-31VDC...
  • Page 45 COMPATIBLE ACCESSORY DEVICES Mfg. Order No. Description Cat. No. FARADAY INC. R711-1 711-1 Remote Relay Unit 15222A 15222A Signal Expander Panel 5405 SYNC Control Module 5406 SYNC Control Module RSE-100 15070 Remote Signal Extender Notes: The accessory devices listed above may be wired to activate from the signal circuit.
  • Page 46: Wire Selection Guides Iii-31

    WIRE SELECTION GUIDES INITIATING CIRCUIT WIRE SELECTION GUIDE Each initiating circuit loop must not have a resistance greater than 100 ohms. The following chart is based on the resistance of solid copper wire. MAXIMUM WIRE LOOP DISTANCE (ft.) 22 AWG 20 AWG 18 AWG 16 AWG...
  • Page 47: Battery Size Calculations Iii-32

    BATTERY SIZE CALCULATIONS STANDBY ALARM CURRENT CURRENT (A.) (A.) CONTROL UNIT (2 ZONES) .025 .110 ADD FOR A 4 ZONE CONTROL UNIT +.010 +.080 OPTIONAL MODULES 15212 - REMOTE ANNUNCIATOR MODULE +.002 +.050 7704 ANNUNCIATOR +.022 +.092 15213A - MARCH TIME/TEMPORAL SIGNALING +.050 15219 - ZONE RELAY MODULE +.115...
  • Page 48 J2 and main board connectors J6 & J7 with the colored rib on the dot at each connector NOTE: J7 is not used on 15220A control units. CAUTION: Check to see that the connectors are properly seated on all of the pins.
  • Page 49 Form "C" contact configuration (contacts shown in normal standby condition; transfer for operated condition). Trouble contacts for power limited source rated 1A. @ 28 V.D.C., resistive. TYPICAL 7700 SERIES ANNUNCIATOR Not supervised AND TROUBLE UNIT WIRING General alarm contacts for power limited 7704 ANNUNCIATOR source rated 5A.
  • Page 50 CAT. NO. 15213A MARCH TIME/TEMPORAL SIGNALING MODULE The 15213A March Time / Temporal Signaling Module is an optional module for the 15220A or 15240A Fire Alarm System Control Unit. This module provides programming capabilities for the control unit's signal circuit (Note: This module doesn't provide two additional signal circuits).
  • Page 51 CIRCUIT #1 POWER LIMITED SUPERVISED Alarm Ratings: 2.5A. max. (combined circuit #1 + #2) Note #5 Use only compatible signals specified in owners manual. CIRCUIT #2 POWER LIMITED SUPERVISED + OR RED - OR BLK NOTES 1.) Units to be installed in accordance with the National Electrical Code and / or local electrical codes.
  • Page 52 INSTALLATION INSTRUCTIONS AND WIRING FOR CAT. NO. 15219 ZONE RELAY MODULE The 15219 Zone Relay Module is an optional module for the 15220(A) or 15240(A) Fire Alarm System Control Unit. This module provides a form "A" zone alarm contact per zone, a form "A" general alarm contact, and a form "B"...
  • Page 53 Zone alarm contacts for power limited source rated 1A. @ 28 V.D.C., resistive. Not supervised General alarm contacts for power limited source rated 5A. @ 30 V.A.C. / V.D.C. Not supervised Form "A" Form "B" Typical contact configurations (contacts shown in normal stand-by condition; transfer for operated condition).
  • Page 54 INSTALLATION INSTRUCTION AND WIRING FOR CAT. NO. 15209 CITY TIE MODULE The 15209 City Tie Module is an optional module for the 15220(A) or 15240(A) Fire Alarm System Control Unit. This module provides an alarm / trouble transmitter and a form "C" system trouble contact. The module also contains a city tie disconnect switch and a yellow trouble / off-normal switch L.E.D.
  • Page 55 Alarm Remote Station Transmitter Circuit (Power Limited) 16.5 - 28. V.D.C., 14mA. max. 1.2V. Ripple max. Polarity shown for normal standby condition. Polarity reversed for alarm condition, open circuit for trouble conditions. Trouble contacts for power limited source rated 1A. @ 28 V.D.C., resistive. Not supervised Form "C"...
  • Page 56 INSTALLATION INSTRUCTION AND WIRING FOR CAT. NO. 15215 CITY TIE/AUXILIARY RELAY MODULE The 15215 City Tie / Auxiliary Relay Module is an optional module for the 15220(A) or 15240(A) Fire Alarm System Control Unit. This module provides a supervisory / trouble transmitter, an alarm / trouble transmitter or a local energy city box trip circuit, a form "C"...
  • Page 57 Supervisory Remote Station Transmitter Circuit (Power Limited) 16.5 - 28 V.D.C., 14mA. max. 1.2V. Ripple max. Polarity shown for normal standby condition, Polarity reversed for alarm condition (zone #1 only). Open circuit for trouble condition. See below for alarm circuit wiring of Alarm Remote Station Transmitter Circuit or Local Energy City Box Trip Circuit.
  • Page 58 INSTALLATION INSTRUCTION AND WIRING FOR CAT. NO. 15217 AUXILIARY RELAY MODULE The 15217 Auxiliary Relay Module is an optional module for the 15220(A) or 15240(A) Fire Alarm System Control Unit. This module provides a form "C" trouble contact and a form "C" general alarm contact. The module also contains a disconnect switch and a yellow trouble / off-normal switch L.E.D.
  • Page 59 Trouble contacts for power limited source rated 1A. @ 28 V.D.C., resistive. Not supervised General alarm contacts for power limited source rated 5A. @ 30 V.D.C. / V.A.C. Not supervised Form "C" contact configuration (contacts shown in normal standby condition; transfer for operated condition).
  • Page 60 INSTALLATION INSTRUCTIONS FOR CAT. NO. 15207 SUPERVISORY MODULE The 15207 Supervisory Module is an optional module for the 15220(A) or 15240(A) Fire Alarm System Control Unit. This module provides a separate, audible indication of a supervisory condition in Zone #1 of the Control Unit.
  • Page 61 INSTALLATION INSTRUCTIONS FOR CAT. NO. 15206 D.A.C.T. INTERFACE MODULE The 15206 D.A.C.T. Interface Module is an optional module for the 15220(A) or 15240(A) Fire Alarm System Control Unit. This module provides a form "C" trouble contact, a form "C" alarm contact, a form "C" superavisory contact, a form "C"...
  • Page 62 Form "C" contact configuration (contacts shown in conduit and may not exceed 20 feet. normal standby condition: transfer for operated condition). FARADAY DC-100/101 NOTES: Units to be installed in accordance with the National Electrical Code and / or local electrical codes.
  • Page 63: Mcculloh Transmitter Connections Iii-48

    McCULLOH TRANSMITTER CONNECTIONS The 15220(A) or 15240(A) Fire Alarm System Control Unit can be wired in conjunction with a Potter Electric Signal Co., Model EFT-C Alarm Transmitter, to provide central station, proprietary, or remote station service. The 15217 Auxiliary Relay Module is also required to provide a general alarm contact and trouble contact. If alarm transmission by zone is required, the 15219 Zone Relay Module may be used in conjunction with additional transmitters.
  • Page 64 TROUBLESHOOTING GUIDE CAUTION: Fire alarm system troubleshooting and repairs are to be done only by qualified service technicians The 15208 Troubleshooting Module is used to aid in locating any main board troubles except zone troubles. The following steps should be used.
  • Page 65: Troubleshooting Guide (For Quailified Personnel Only)

    TROUBLESHOOTING GUIDE (Cont'd) INDICATOR POSSIBLE PROBLEMS POSSIBLE SOLUTIONS Main Board Troubles Zone Trouble 1.) Open initiating circuit wiring 1.) Correct wiring fault 2.) Loss of power to 4-wire smoke detectors 2.) A.) Restore smoke detector power B.) Correct wiring fault 15208 Troubleshooting Module Brown-Out 1.) Low 120 V.A.C.
  • Page 66: Option Module Troubles

    TROUBLESHOOTING GUIDE (Cont'd) INDICATOR POSSIBLE PROBLEMS POSSIBLE SOLUTIONS Option Module Troubles 15212 Remote Annunciator Module Trouble 1.) Open annunciator wiring 1.) Correct wiring fault 2.) Activated annunciator indicator 2.) A.) Operate SYSTEM RESET switch B.) Return the anunciator LAMP TEST switch to normal 15209 City Tie Module Trouble 1.) DISCONNECT switch operated...