Faraday MPC-6000 Programming Manual page 16

Fire alarm system control unit
Table of Contents

Advertisement

M P C - 6 0 0 0
/
M P C - 7 0 0 0
Monitor Modules with relay and single input
Parameter
Label
Generic label identifying the detector by loop number and address.
Led off
LED will be defaulted to ON.
Input Usage
Input usage will be defaulted to alarm.
Input Group
Inputs will be defaulted to input group 241 (General Alarm).
Network Group
This will not be set and will need to be set manually. (Future use)
Output Type
Will be defaulted to non-silenceable.
Output Zone
Will be defaulted to 1.
Intelligent LEDs
Parameter
Label
Generic label identifying the detector by loop number and address.
Output Type
Will be defaulted to non-silenceable.
Output Zone
Will be defaulted to 1.
NACs
Parameter
Notification
Set to Audible.
Device Type
Output Type
Will be defaulted to silenceable.
Output Zone
Will be defaulted to 1.
Always On
Will be no.
Wire Class
Will be defaulted as Class B.
Default Times
ON time delay will be defaulted to no delay.
OFF time delay will be defaulted to no delay.
The ON time and OFF time refer to the time delays in which the NAC delays its activation and
deactivation.
System Parameter
Parameter
Label
Drill Enable
Auto Silence Timer
Alarm Silence Inhibit
Panel Reset Inhibit
Auto Alarm silence
Trouble Reminder
NAC sound time
Quick test exit
City Tie Activation
Global Commands
Printer ESC
Releasing
The presence of RDC-2 Annunciators is detected and their address is programmed
automatically when the system is initialized.
/
R N D - 2
P R O G R A M M I N G
Set to "FARADAY AUTO Prgrmd"
ON
Off
Off
Off
Off
12 hours
5 seconds
30 minutes
Not changed
Not changed
Not changed
Not installed. If installed, this activates releasing application features.
12
M A N U A L
Description
Description
Description
Description