Configuring the Remote LCDs (RDC-2s)

Following are the steps that need to be followed to configure the remote LCD units.
Action
1. Select "Edit".
2. Select "Manual Pgm".
3. Use "Cmor" and select "RS-485 NW".
4. Select "RDC Annciatrs".
5. Enter a "1" in the map to enable the RDC at
the selected address. (Use the * and # buttons to
navigate left and right.)
6. Press Bsav to save the selection.
Configuring the Panel Relays
Panel relays are set by default as follows:
Relay 1: Alarm, Non-silenceable, no on- or off- delays
Relay 2: Pre-alarm, Non-silenceable, no on- or off- delays
Relay 3: Supervisory, Non-silenceable, no on- or off- delays
Relay 4: Trouble, Non-silenceable, no on- or off- delays
In the default configuration, any Alarm, Trouble, etc., on the system will activate the
corresponding relay.
Following are the steps that need to be followed to configure the panel relays differently
than the default settings.
Action
1. Select "Edit".
2. Select "Manual Pgm".
3. Select "Cmor".
4. Select "Cmor".
5. Select "Prgm Relays".
6. Follow the screen prompts to set up the panel relays.
7. Press Bsav to save the selection.
These are the parameters that need to be set when configuring panel relays.
Installed
Select yes to program independently.
Output Zone
Enter the number of the output zone that activates this circuit.
Output Type
Select the type of event and whether or not it can be silenced.
Delay Timers
Allows the setting of activation and deactivation times for the relay. The On delay
sets the time after the event that the relay will activate. The Off delay determines
how long it will stay on after it activates. The times are in seconds.
NOTE: When a programmable relay is set for "AC Power Fail," the system trouble group must activate the
same output zone assigned to the relay.