Last Event Record (Test Level 4)
This feature records the zone in which the
last event occurred in each of four catego-
ries: Alarms, Troubles, Verified Alarms, and
Supervisories. This can be used for trouble-
shooting one-time reports of events.

Program Mode

The program mode allows the user to
change the configuration of the LW-401
system. The program mode has nine levels.
Each level allows the user to configure a
different function within the LW-401.
When the program mode is enabled, the
current programming levels and sublevels
display in turn on the seven segment display.
The order of the display is as follows:
1. the program level is displayed first
2. then a hyphen (-) is displayed
3. then the sublevel is displayed
4. then the display is blank.
The entire sequence then repeats.
In the programming mode, the four function
keys operate differently than they do in the
normal mode. Their functions are as follows:
The Acknowledge key toggles between the
Test mode, the Program mode, and the
Leave mode. The seven segment display
shows t, P, and L, respectively, to indicate
these modes.
The Reset key is used to select program
levels and options inside the programming
levels.
The Drill key selects options and toggles
options on and off.
The Silence key selects different sublevels.
Pressing silence when the seven segment
display shows L exits the user from the
program/test mode.
LW-401
LW-401 Operation, Installation, and Maintenance Manual

PROGRAM LEVEL DESCRIPTIONS

Level 1:
Bypass or enable the LWZE-4A or
LWZE-8A Zone Expander card.
Level 2:
Bypass or enable the Relay and/or
the Open Collector Outputs on the
optional LWZE-4A, or LWZE-8A
and LWZR-8 cards.
Level 3:
Allows configuration of the Initiat-
ing Zone Circuits to any one of
the following types: Initiating,
Verified Initiating, Supervisory,
and Generic Input.
Level 4:
Allows configuration of the Notifi-
cation Appliance Circuits to Non-
Silenceable and any one of the
following types: Steady, Tempo-
ral, March Time, and Simplified
Zone Code.
Level 5:
Allows programming of the out-
puts on the optional LWZE-4A or
LWZE-8A Zone/Output Expander
card and the LWZR-8 Relay card
to follow Alarms on the Initiating
Zone Circuits.
Level 6:
Allows programming of timer and
counter values:
• the Verification Timer between
15 and 50 seconds.
• the Inhibit and Cutoff Timers
of the Notification Appliance
Circuits.
• the Round Count ranging from
3 to 8 for Simplified Zone Coding.
Level 7:
Allows programming of the 4-digit
Password.
Level 8:
Allows programming of the AC
Fail Trouble Signal Delay.
Level 9:
Enable/Disable the LWZR-8;
LWRA-8B/W, Addresses 1 and 2;
LWCT-1; and LWZE-4A/
LWZE-8A.
15