Installing the DACT

Setting the System Reporting Type must be selected before installing the DACT. See
page 36. Following are the steps that need to be followed to install the DACT.
Action
1. Select "Edit".
2. Select "Manual Pgm".
3. Select "Outputs".
4. Use "Cmor" and select "Option Mods".
5. Select "DACT CFG".
6. Follow the screen prompts to set up the DACT.
These are the parameters that need to be set when installing the DACT.
Test Time
Select the line number
Select the dialing method

Configuring the DACT Accounts

Following are the steps that need to be followed to configure the DACT Accounts.
Action
1. Select "Edit".
2. Select "Manual Pgm".
3. Select "Outputs"
4. Use "Cmor" and select "Option Mods".
5. Select "DACT ACCTS".
6. Follow the screen prompts to set up the DACT
Accounts.
The following information is set up for the two possible DACT accounts.
Format
This is the format that is used to report to the Central station. The options are
SIADCS8, SIADCS20, ADEMCO, 4/2-1400, 3/1-1400, 3/1-2300, 4/2-2300.
Number of
This is the number of times that the DACT will attempt to dial the account before
attempts
trying the next account.
Must report
When selected yes, the DACT must report these events to the selected account "x".
event type
If not selected and the DACT cannot report the event to account "x" for whatever
reason, it will try a different account "y". If it successfully reports it to account "y", it
will not go back to account "x" and try again. If Must Report is selected, it will keep
trying to report to account "x" until it is successful, whether or not it has already
successfully reported it to a different account.
Account
The number to identify the account at the central station.
number
CIC prefix
The prefix used by the DACT to dial through a PBX to access a line.
Phone
The phone number which the DACT will dial for this account.
number
/
R N D - 2
P R O G R A M M I N G
The time that the DACT will regularly call in to the central station to check the
connection.
The DACT can connect to two lines. Select which one is to be configured.
The DACT can dial using pulse or tone. Select which is needed.