Configuring The Coder; Setting System Timers - Faraday MPC-6000 Programming Manual

Fire alarm system control unit
Table of Contents

Advertisement

Configuring the Coder

Following are the steps that need to be followed to configure the Coder.
Action
1. Select "Edit".
2. Select "Manual Pgm".
3. Select "Outputs"
4. Select "Cmor" twice and select "Option Mods".
5. Select "Cmor".
6. Follow the screen prompts to set up the Coder.
These are the parameters that need to be set when configuring the coder.
NOTE: The Coder is not available if Releasing Group is being used.
None
If none is selected, only the predefined bell codes (Steady on, March Time,
Temporal, California, Three-pulse Temporal and Alert) may be selected for the
Alarm Bell Code for any input group.
Zone Coder
If selected, coder may be selected for the Alarm Bell Code for any input group in
addition to the predefined bell codes.
Master Coder
If selected, this code will be used for the Alarm Bell Code for all input groups.
Predefined and user configured bell codes will not be available for the Alarm Bell
Codes.
Play after
This is the bell code (MTB, Temporal, Steady, None) that will be played after the
Code
Master Code.
Master Code
These are the digits used in the Master Code. Up to four code digits may be
entered. Zero is used as an "end of code" indicator. For example, to set the code to
2-4, enter "2" for the first digit, "4" for the second and "0" for the third.
Rounds
Number of rounds of a bell code that will be played (3, 4 or Continuous). If "3
rounds" is selected, the bell code will play three times then will change to the code
selected in Play after Code. If "Continuous" is selected, the bell code will play
continuously until silenced.

Setting System Timers

Following are the steps to set system timers.
Action
1. Select "Edit".
2. Select "Manual Pgm".
3. Use "Cmor" and select "Sys Params".
4. Use "Cmor" and select "Timers".
5. Use "Cmor" to select the timers to be set.
Below is a list of the timers and their functions:
Parameter
Alarm Silence Inhibit
Panel Reset Inhibit
Trouble Reminder
Quick test NAC time
Quick test exit
M P C - 6 0 0 0
/
M P C - 7 0 0 0
Description
The period of time that the alarm will sound before it can be silenced.
The period of time that the panel is prevented from being reset after an
alarm is annunciated.
The time period before a trouble will come back to remind the installer.
The length of time that the NACs will sound in Quickest.
The time that Quick test will exit automatically after inactivity.
35
/
R N D - 2
P R O G R A M M I N G
M A N U A L