Configuring The Remote Relays (Srus); Configuring The Remote Leds (Slus) - Faraday MPC-6000 Programming Manual

Fire alarm system control unit
Table of Contents

Advertisement

M P C - 6 0 0 0
/
M P C - 7 0 0 0
Parameter
Output Type

Configuring the Remote Relays (SRUs)

Following are the steps that need to be followed to configure the remote relay units.
Action
1. Select "Edit".
2. Select "Manual Pgm".
3. Select "Outputs".
4. Select "SRUs".
5. Enter the address of the relay to be configured
6. Enter a "1" to enable the relay.
The relays in the serial relay unit must be logically connected to an output zone in order
to operate. When the selected output zone becomes active, the relay will become active
based on the type of activation that has been selected, i.e., alarm, trouble, supervisory,
pre-alarm. Set the output type and the output zone that will activate this relay.

Configuring the Remote LEDs (SLUs)

Following are the steps that need to be followed to configure the remote LED units.
Action
1. Select "Edit".
2. Select "Manual Pgm".
3. Select "Outputs".
4. Select "SLUs".
5. Enter the address of the LED to be configured.
6. Enter a "1" to enable the LED. (Use the * and #
buttons to navigate left and right.)
The LEDs in the serial LED unit must be logically connected to an output zone in order
to activate. When the addressed output zone becomes active, the LED will become
active depending on the type of activation that has been selected, i.e., alarm, trouble,
supervisory, pre-alarm. Set the output type and the output zone that will activate this
LED.
/
R N D - 2
P R O G R A M M I N G
Description
Alarm Silenceable, Alarm Non-Silenceable, Pre-Alarm Silenceable,
Pre-Alarm Non-Silenceable, Trouble Silenceable, Trouble Non-
Silenceable, Supervisory Silenceable, Supervisory Non-Silenceable,
Releasing NAC.
Note: Use Trouble or Supervisory NAC output type only where required.
If the Output Type Releasing NAC is selected, another screen will open
to prompt the user if this particular releasing NAC will activate on 1
Alarm, Discharge or Pre-Discharge.
Select ON if the NAC is to activate. When 1
is selected, all other NAC outputs must be configured as Steady-On
only bell code.
32
M A N U A L
st
Alarm/Pre-Discharge NAC
Result
The user may now navigate through screens
that allow setting the parameters of the
address relay.
Result
The user may now navigate through screens
that allow setting the parameters of the
address LED.