FRESH AIR INLET KIT 55200305

This kit is for use on all CC875 indoor units to provide fresh air to the conditioned space.
ITEM
QTY
1
1
2
4
The maximum fresh air that can be introduced into the unit is 5% of the total air volume.
It is easier to fit this kit prior to installing the unit.

ISOLATE THE SYSTEM ELECTRICALLY PRIOR TO INSTALLATION OF THIS KIT

1. Pull out and discard the plastic blanking cap from the relevant corner, (DO NOT CUT THE POLYSTYRENE).
2. Replace with the fresh air supply duct (with the flange nearest the false ceiling when the unit is installed) and
secure using the four screws provided.
3. The installer must provide ductwork, a screened source of fresh air and an auxiliary fan.
4. An an auxiliary fan must be sized to overcome the resistance of the filter, the ductwork and the IMAGE 875 unit
itself. (To prevent excessive noise, the maximum fresh air volume should be 10% of the nominal air volume for
any given unit and fan speed)
5. The auxiliary fan should be connected to a separate electrical circuit, appropriately fused and isolated.