Bms Alarm Interface Kit 53800423 - Marstair CC 875 Technical Manual

Cassette split systems
Table of Contents

Advertisement

BMS ALARM INTERFACE KIT 53800423

By fitting a BMS alarm interface kit, a simple common alarm signal is available for volt free input to a BMS network.
Power failure, or any other notifiable alarm state, causes the output relay to de-energise.
Condition OK
= system running without fault
Condition Alarm = system mains power loss or notifiable alarm state.
ITEM
No DESCRIPTION
1
1
BMS Alarm Interface Board
2
4
Mounting Foot (self adhesive for IMPACT-E)
3
4
Mounting Foot (hook type for IMAGE-E)
MOUNTING
1 After gaining access to the electrics panel, fit 3 long mounting feet to the pcb.
2 Connect the wires as shown.
Tel: 01823 665660
Heronhill - for all your Marstair requirements
55
www.heronhill.co.uk
ITEM
No DESCRIPTION
Mounting Foot (long: 4 for IMAGE 600E,
4
4
3 for CC875E)
5
1
Orange Wire
6
1
Yellow Wire
Fax: 01823 665807