CXE Pump Down units are fitted with an expansion assembly and solenoid valve These units must be ran on a liquid line and matched with the Marstair CKC Pump Down units which are fitted with a liquid receiver.
CX(E) DIMENSIONS 888 (Fixing centres) 17.5 TOP VIEW (Ceiling Mounted) 17.5 MIN. MIN. SIDE VIEW FRONT VIEW SIDE VIEW (Wall mounted) (Wall mounted) (Ceiling mounted) X = Interconnecting Wiring = Suction MIN. 500 = Liquid / Expansion FOR SIDE ACCESS 65 TYP.
INSTALLATION CONTENTS PARTS DESCRIPTION ACTION Envelope containing operating instructions and Pass to the end user. Declaration of Conformity Mounting brackets Use to hang unit. Drain Stub/Nut/Gasket Fitted by installer. Drain stub adaptor Convert to ¾" drain if required. Screw M5 To fix brackets to unit.
Page 9
MAXIMUM EQUIVALENT LENGTH OF SUCTION LINE PIPE SIZES (m) LIQUID LINE SYSTEM 3/8" 1/2" 5/8" 3/4" 7/8" 1/4" 3/8" 1/2" CX(E)40 + CKC20 CX(E)50 + CKC40 CX(E)70 + CKC60 CX(E)90 + CKC80 PIPE CONNECTIONS Units are supplied with the following male flare connections (sizes in inches): INDOOR UNIT CX(E)30 CX(E)40...
RESTRICTORS Indoor units are supplied with restrictors fitted. NOTE When the CXE 40 is matched with a CKC 20. The restrictor in the indoor unit must be changed to 0.033" When the CXE 50 is matched with a CKC 40. The restrictor in the indoor unit remains as a 0.050"...
Page 11
Liquid line Expansion line Charge 1/4" 3/8" 3/8" 1/2" 5/8" based on:- 25 g/m 60 g/m 16 g/m 30 g/m 48 g/m Additional POE oil 25g per 350g of additional refrigerant to a maximum of 300g NOTE: The new 50 Series CKC are supplied with a Nitrogen holding charge. See pages 12 & 13 for refrigerant charge information.
CXE PUMP DOWN 17 SERIES MATCHED WITH CKC 50 SERIES UNITS WITH MICROCHANNEL COIL Part Number Liquid Line System CX(E)30 + CKC20 55917006 55050800 1079 1204 CX(E)40 + CKC30 55917007 55050801 1034 1334 1634 1934 2234 2534 2834 3134 3434 R407C CX(E)50 + CKC50 55917008 55050803...
WIRING DIAGRAM CXE PUMP DOWN Note: Only 'Mains in' supply needs connecting when running system on pump down, no need to connect to 'CU OUT' Terminals 13/19 55908061-01...
Page 14
CKC PUMP DOWN Note: Only 'Mains in Live, Neutral & Earth' supply needs connecting when running system on pump down, no need to connect to 'Remote thermostat -8' or 'Control wire - 42' or 'To Evaporator unit' Terminals TIMER RELAY SETTINGS Note: Set for minimum compressor off time, minimum 30 seconds 14/19 55908061-01...
CXE ELECTRONIC COOLING SYSTEM CONTROLS CAREL IR33 Controller ON/OFF SWITCH The switch operates the fan motor and is illuminated when power is supplied to the indoor unit. When switched OFF, the fan stops, the switch remains illuminated and the crankcase heater in the outdoor unit (if fitted) remains live. Minimum Set Temperature 8°C Minimum Set Temperature 4°C INDOOR UNIT OUTDOOR UNIT...
CKC INSTALLATION MOUNTING Whether floor or wall mounted, it is essential that the mounting surface is capable of supporting the unit weight. Leave space around the unit for air circulation and access for installation and maintenance. Dimensions in mm. MODEL CKC 20 CKC 30 CKC 40...