P90L 6kVA & 10kVA User's Manual
Specifications
MODEL NUMBER
CAPACITY
AC output
INPUT
Voltage
Frequency
OUTPUT
Voltage
Frequency
THD (full load)
Overload capacity
Crest factor
BATTERY
Charger amps
CHARGER
Nominal/float voltage
UPS dimensions (W x D x H)
PHYSICAL
UPS weight
Input connection
Output connection
ENVIRONMENT Efficiency
Operating temperature
Audible noise
Altitude
Model number
OPTIONAL
BATTERY PACKS Dimensions (W x D x H)
Weight
Battery quantity/type
Dimensions (W x D x H)
OPTIONAL
TRANSFORMER Weight
APPROVALS
WARRANTY
COMMUNICATIONS INTERFACE
INCLUDED IN BOX
AVAILABLE OPTIONS
*Depending on load level
**P90L capacity derates 10% at 200VAC output voltage
Frequency converter derates capacity 40%
Xtreme Power Conversion Corporation
P90L-6K
6kVA (5.4kW)
200/208/220/230/240VAC**
240/120VAC with optional isolation transformer with maintenance bypass
110% 10 min; 130% 1 min; > 130% 1 sec
17.2 x 26.3 x 5.3 in
55 lbs
Terminal block with 6 ft, L6–30P
Terminal block with 3 ft, L6–30R
Up to 98% ECO mode and 92% online mode
< 58dBA
11,500 ft above sea level
17.3 x 28.7 x 3.5 in
99 lbs
3 years electronics and battery (2 years outside of USA)
RS-232, USB, EPO, intelligent slot for optional cards
(Web/SNMP, Relay/dry contact, Modbus)
Software CD, horizontal brackets, tower pedestals
5 year extended warranty, power distribution (XPDU), 4-post rail kit,
2-post shelf kit, isolation transformer with maintenance bypass
Uninterruptible Power Supply
P90L-10K
10kVA (9kW)
110–300VAC*
50/60Hz
50/60Hz ± 4Hz
< 2%
3:1
4A
240/270VDC
17.2 x 29.5 x 5.3 in
60 lbs
Terminal block
Terminal block
32–104°F (0–40°C)
< 60dBA
P90L-BP240
17.3 x 25.1 x 5.3 in
165 lbs
(20) 12V9AH/240V
17.3 x 31.8 x 5.2
122 lbs
UL, cUL, RoHS
Page 30
Need help?
Do you have a question about the P90L-ISO6MB and is the answer not in the manual?