M90S Service Manual
2. Electric Specifications
Input
Input Voltage
Input Frequency
Input Power Factor
Input THD(Full Load)
Generator
Output
Output Power (VA/Watt)
Nominal Output Voltage
Voltage Regulation
Output Frequency
Voltage Distortion
Current Crest Ratio
Transfer Time
Short Circuit Protection
Battery
Nominal Battery Voltage
Acceptable Battery
Quantity (PCS)
Type/Capacity
Backup Time (minutes)
Efficiency
Line Mode
Battery Mode
ECO Mode
Xtreme Power Conversion Corporation
Follows Bypass Frequency if the bypass is ok(except the convert mode)
(50/60+0.1) Hz if bypass is not ok or in convert mode
3:1max
0ms @ Line <> Battery
0ms @ Inverter <> Bypass
<10ms @ Inverter <> ECO
Yes
+/- 96~120V
(8~10)×12V/pc*2
12V/9Ah or equivalent
>5 mins @ +/- 8 pcs
Batteries
>7 mins @ +/- 10 pcs Batteries
91
90
>97%
Uninterruptible Power Supply
88~155
VAC(L-N)
46~54 Hz for 50Hz system
56~64 Hz for 60Hz system
≥ 0.99 @100% R/RCD Load
≥ 0.97 @ 50% R/RCD Load
<4%@ Linear load
Support
6000VA/6000W
100/110/115/120/
127VAC(L-N)
<1%(balance load)
<2% (unbalance load)
≤4%
for nonlinear load
≤2% @ Full Linear Load
Page 5