• Next delay input (y=5) provides entrance delay only if at the moment of its triggering the entrance delay has been in
progress (activated before by any delayed input). If no delayed input is triggered before next delayed, the triggering
will cause an instant alarm.
• Addressing of inputs to section C when the control panel is not split has the same effect as addressing to section B
(i.e. automatic bypass while partial arming is used).
• If y=6 is programmed, then each triggering of this input changes arming status (arm – disarm – arm...) of the entire
system or just the corresponding section if the system is split.
Example: to set zone 2 input as a balanced loop with an instant reaction, addressed to section A, enter: 60 02 201
Factory default setting: L1 = delay, L2 = next delay, L3 = instant, L4 = tamper
10.3 Exit / Entrance delay
To change the duration of the exit and entrance delay (both of them) enter
21x
(where x represents time in seconds x10). The delay can be selected from 10 to 90 seconds.
Example: to select an Exit and Entrance delay duration of 20 seconds, enter 212
Factory default setting is 30 seconds
10.4 Alarm duration
The alarm duration can be selected from 1 to 8 or 15 minutes entering:
22x (where x=time in minutes for1 to 8, x=9 means 15 minutes and x=0 means 10 seconds)
Example: to select an alarm duration of 15 minutes, enter 229
Factory default setting is 4 minutes
10.5 PgX and PgY output functions
The control panel outputs PgX and PgY can have different functions, depending on parameter x in the corresponding
sequence:
2 3 x – determines triggering of PgX
2 4 x – determines triggering of PgY
where x represents the following functions (non split system):
0 Chime – triggered during the entrance delay (pre-alarm output)
1 Fire – triggered by a fire alarm (by a smoke or a gas detector)
2 Arm – activated when the control panel is armed (complete & partial arming)
3 Panic – activated when a silent panic alarm is triggered
4 Alarm – triggered by any audible alarm (except panic alarm)
5 Door – activated for 5sec. after
6 Home – activated when the control panel is partially armed (Home arming)
7 No AC – triggered by an AC power failure
8 Phone/F8 – output can be operated remotely by phone or by SMS (if this feature is supported by installed communicator) or
locally from the keypad by F81 (ON) and F80 (OFF). If a code is requested to operate the system (see 10.12) then the F8x
instruction should be followed by a valid user code.
Note: the control panel also wirelessly transmits the PgX and PgY signals. Wireless output modules UC-216 and UC-222
can be used to receive the signals (see 10.11). The function of the UC module output relays is determined by the 23x and
24x setting.
Example: the PgX will work as a Panic output when 233 is entered, PgY as Door output when 245 is entered.
Factory default setting: PgX=Chime, PgY=Arm

10.6 Recorded message and phone number editing in the user mode

The User mode, which is accessible with F 0 "Master Code", is for bypass setting, system testing and battery
replacement. This setting enables the user to change the voice message and telephone numbers of the built in dialer. If
the changes are enabled, then programming sequences for number programming, voice message recording and dialer
testing are accessible in the User mode. These settings have effect only when the control panel has a telephone
communicator module.
options:
2 5 1
2 5 0
Factory default setting: changes disabled
JA-63 „PROFI" Alarm System
(F3) entering (electric door lock opening)
changes enabled
changes disabled (no dialer programming in the User mode)
- 11 -
sequence: 2 1 x
sequence: 2 2 x
sequences: 2 3 x & 2 4 x
If the system is split:
23x
24x
x
(PgX)
(PgY)
0
Alarm A
Alarm A
1
Alarm B
Alarm B
2
Chime A
Chime A
3
Chime B
Chime B
4
Arm A
Arm B
5
Door A
Door B
6
Panic A
Panic B
7
FIRE
No AC
8
Phone/F8
Phone/F8

sequence: 2 5 x