12. Install the vertical termination—The final step involves
installation of the SV4.5CGV-1 vertical termination. Align
the termination over the end of the previously installed
section, adjusting the radial alignment until the four (4)
locking dimples of the termination are aligned with the
inlets of the four (4) incline channels of the last vent sec-
tion. Push the termination down until it fully engages, then
twist the termination clockwise running the dimples down
and along the incline channels until they seat at the end of
the channels. If the vent system extends more than 5 ft (1.5
m) above the roof flashing, stabilizers may be necessary.
Additional screws may be used at section joints for added
stability. Guide wires or roof support assemblies may be
attached to the joint for additional support on multiple joint
configurations.
NOTE: SV4.5VF firestop/spacer must be used anytime vent pipe pass-
es through a combustible floor or ceiling. SV4.5HF firestop/spacer
must be used anytime vent pipe passes through a combustible wall.
Horizontal overhang
2 ft minimum
Vent
termination
H*
Storm collar
Flashing
1" (25.4 mm) minimum
clearance to combustibles
Concentric
*H = minimum height from roof to
vent pipe
lowest discharge opening of vent
Roof
Pitch
Flat to 6/12
6/12 to 7/12
7/12 to 8/12
8/12 to 9/12
9/12 to 10/12
10/12 to 11/12
11/12 to 12/12
12/12 to 14/12
14/12 to 16/12
16/12 to 18/12
18/12 to 20/12
20/12 to 21/12
Figure 22 - Termination Heights for Vents above Flat or Sloped
Roofs (NFPA 54 / ANSI Z223.1)—Gas Vent Rule
126718-01C
VENTING INSTALLATION Continued
2 ft
Vertical
minimum
wall
Lowest
discharge
opening
X
12
Roof pitch is X/12
Termination
Height *
1.0 ft (0.3 m)
1.25 ft (0.38 m)
1.5 ft (0.46 m)
2.0 ft (0.61 m)
2.5 ft (0.76 m
3.25 ft (0.99 m)
4.0 ft (1.22 m)
5.0 ft (1.52 m)
6.0 ft (1.83 m)
7.0 ft (2.13 m)
7.5 ft (2.29 m)
8.0 ft (2.44 m)
Superiorfireplaces.US.com
Vertical termination Configurations
Figure 23 and 24 show the configurations for vertical termination.
Ceiling
firestop/spacer
SV4.5VF
Figure 23 - Top Vent—Straight
Venting with Two 90° Elbows
Vertical (V
)
Horizontal (H)
1
5' Min.
10' Max
6' Min.
14' Max
7' Min.
20' Max
20' Max.
20' Max
Note:
Vertical (V
) + Vertical (V
) = 20' Max.
1
2
V + H = 40' Max.
H=20' Max.
Figure 24 - Vertical Venting Configuration Using Two 90° Elbows
40 ft. maximum
90°
Elbow
19