Mantel And Wall Projections - Heatilator ECLIPSE-32 Installation Manual

Hide thumbs Also See for ECLIPSE-32:
Table of Contents

Advertisement

B. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear-
ances as specifi ed. Framing closer than the minimums listed
must be constructed entirely of non-combustible materials
(i.e., steel studs, concrete board, etc.).
Note: Measurement is taken from top of the
opening, NOT the top of the fi replace.
Note: All
measurements
in inches.
6
5
4
3
4
TOP OF HOOD OR FIREPLACE OPENING
Figure 10.3 Clearances To Combustibles Mantels Or Other
Combustibles Above Appliance
TOP VIEW
FIREPLACE OPENING
See Dimension B on Appliance
Dimension Diagram (Figure 3.1).
Note: Clearance from
opening to perpendicular wall.
Figure 10.4 Non-Combustible Mantel Leg or Wall Projections
(Acceptable on both sides of opening)
CEILING
12
11
10
9
8
32
7
13
12
11
10
9
8
7
6
5
MEASUREMENTS FROM
TOP EDGE OF THE OPENING
See Dimension V on Appliance
Dimension Diagram (Figure 3.1).
1/2 IN.
MINIMUM
2-7/8 IN.
MINIMUM
3 FT. MAXIMUM
Heatilator • ECLIPSE-32, ECLIPSE-36 Installation Manual • 2297-984 Rev. B • 6/15
FIREPLACE OPENING
See Dimension B on Appliance
Dimension Diagram (Figure 3.1).
Note: Clearance from
opening to perpendicular wall.
Figure 10.5 Combustible Mantel Leg or Wall Projections
(Acceptable on both sides of opening)
3-1/2 in.
1/2 in.
NON-COMBUSTIBLE ZONE
Figure 10.6 Non-Combustible Zone
3 IN.
MINIMUM
5-3/8 IN.
MINIMUM
UNLIMITED
MANTEL LEG OR WALL PROJECTIONS
1/2 in. SHEETROCK
OR COMBUSTIBLE
MATERIAL
45