Table 13
Typical Operation by Control Circuit Terminal Signal
Description
Power ON
1
⋅Displays frequency reference
value.
REMOTE mode is preset at the
factory.
Output Frequency Display
⋅Switch to output frequency
display.
Forward Jog Run
2
(6Hz)
⋅Close between control circuit
terminals 1 and 11 with 7 and
11 closed to perform JOG run.
⋅Open between terminals 1 and
11, 7 and 11 after verifying
normal operation.
Frequency Setting
3
⋅Input frequency reference
voltage (current) by control
circuit terminal 13 or 14 and
verify the input value by the
digital operator.
Output Frequency Display
⋅Select output frequency monitor
display.
Forward Run
4
⋅Close between control circuit
terminals 1 and 11 to perform
forward run.
Stop
5
⋅Open between control circuit
terminals 1 and 11 to stop
operation.
Key Sequence
Digital Operator Display
U1−01 = 0.00 HZ
REMOTE LED lights. (SEQ, REF)
U1−02 = 0.00 HZ
U1−02 = 6.00 HZ
RUN LED lights. FWD LED lights.
U1−01 = 60.00 HZ
For reference voltage 10V
U1−02 = 0.00 HZ
U1−02 = 60.00 HZ
RUN LED lights. FWD LED lights.
U1−02 = 0.00 HZ
STOP LED lights.
(RUN LED blinks during
4
OPERATION
Frequency Ref
Output Freq
Output Freq
RUN
Frequency Ref
Output Freq
Output Freq
RUN
Output Freq
deceleration.)
STOP
43