YASKAWA VS?616G5 Owner's Manual page 19

Yaskawa vs?616g5 inverter owner's manual
Hide thumbs Also See for VS?616G5:
Table of Contents

Advertisement

NOTE
20
indicates shielded wires and
1.
Either control circuit terminal 13 or 14 can be used. (For simultaneous inputs, the two
2.
signals are added internally.)
Control circuit terminal 15/33 of +15 V/−15 V has a maximum output current capacity
3.
of 20 mA.
Multi−function analog output should be used for monitoring meters (e.g. output
4.
frequency meter) and should not be used for feedback control system. Use analog monitor
cards (Model AO−08 or AO−12) for the control system, for a more accurate signal.
When using a braling resistor unit, set the constant L3−04 to "0" (stall prevention level
5.
during decel is "disabled"). If it is not changed, the motor may not stop within the set decel
time.
When using model ERF braking resistor (inverter−mounted type), set the braking resistor
6.
protection selection to "enabled". If it is not changed, the braking resistor cannot be pro-
tected.
When installing a DC reactor (optional for models of 15 kW or below), remove the short−
7.
circuit bar between ¨1 and ¨2 terminals and connect a DC reactor with the terminals.
Select RS−422 or RS−485 of serial communication (terminals 40 to 43) by using the dip
8.
switch on the control PC board. The terminal functions differ between RS−422 and
RS−485.
Table 2
Functions of RS−422 and RS−485
Terminal No.
40
R+
41
R−
42
S+
43
S−
indicates twisted−pair shielded wires.
RS−422
RS−485
Receiver
Receiver
R+/S+
R−/S−
Driver
Driver
R+/S+
R−/S−
Receiver/
Receiver/
Driver
Receiver/
Receiver/
Driver