RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations For The Location Of Fire And Burglary Detection Devices Help Provide Proper Coverage For The Protected Premises. Recommendations for Smoke and Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
Table of Contents SYSTEM FEATURES........................4 MOUNTING THE CONTROL ......................5 WIRING CONNECTIONS........................ 6 AC POWER AND BACKUP BATTERY ..................8 INSTALLING WIRELESS ZONES ....................10 MECHANICS OF PROGRAMMING ..................... 13 ZONE RESPONSE TYPE DEFINITIONS ..................14 DATA FIELD DESCRIPTIONS ..................... 16 *56 ENHANCED ZONE PROGRAMMING MODE..............
LYNXR is not intended for UL985 Household Fire applications. The LYNXR and LYNXR24 are self-contained, rechargeable wireless control/communicators that feature easy installation and usage. A built-in speaker provides voice annunciation of system status along with voice descriptors of each zone (if programmed). The following illustration highlights the main features of this system.
DISCONNECT THIS END ONLY! 01000-003-V0 Desktop Mounting If desired, an optional mounting base (model LYNX-DM, purchased separately) allows the LYNXR and LYNXR24 to be used on a desktop. 1. Slide the control panel onto the mounting base locking tabs 2. Bring all wiring through the bottom of...
Requires the use of an ADEMCO 1332X10 transformer. PHONE LINES Use either the plug-in jacks or the screw terminals. AC TRANSFORMER Use the supplied ADEMCO 1332X10 9VAC, 15VA Plug-in Transformer (1332CN in Canada). 01000-005-V0 EARTH GROUND See Earth Ground paragraph.
Page 7
Connect the com/data/sync/ lines from the HARDWIRED ZONE: If the EOLR is not at the end of the loop, the zone ADEMCO 1332X10 transformer to terminals 9, 13, will not be properly supervised, and the system may not respond to an and 14, respectively.
45 seconds to audibly indicate a low battery condition (press any key to stop the beeping). LYNXR and LYNXR24 are equipped with an integral, replaceable battery pack. Select the appropriate battery based on the installation’s requirement and install the battery pack.
Page 9
AC Power and Backup Battery LYNXR/LYNXR24 AC Power and Rechargeable Backup Battery Replacing the Rechargeable Battery 1. When battery replacement is required, unplug transformer from outlet, and open LYNXR cover. 2. Remove battery retainer and disconnect battery pack connector from receptacle terminal block PC board.
Installing Wireless Zones General Information Zones: The control supports up to 24 wireless zones using 5800 Series transmitters, and up to 16 wireless buttons. Range: The built-in RF receiver can detect signals from wireless transmitters within a nominal range of 200 feet. Transmitters: 5800 Series transmitters have built-in serial numbers that must be entered into the system using the 56 or 83 interactive mode, or input to the control via the downloader.
Page 11
Installing Wireless Zones Transmitter Battery Life • Batteries in the wireless transmitters may last from 4–7 years, depending on the environment, usage, and the specific wireless device being used. Factors such as humidity, high or low temperatures, as well as large swings in temperature may all reduce the actual battery life in a given installation.
Installing Wireless Zones 5800 Series Transmitter Loop Numbers (Refer to this information when programming transmitters) The following illustration shows the compatible transmitters, their associated input types and loop designations. LOOP 3 LOOP 3 LOOP 2 LOOP 4 LOOP 4 LOOP 4 YOU MUST YOU MUST LOOP 2...
Mechanics of Programming General Programming Information Programming options are stored in nonremovable, electrically erasable, nonvolatile EEROM memory. You can program the system at any time, even at the installer's premises prior to the actual installation. Simply apply power temporarily to the Control and then program the unit as desired. There are two programming modes: •...
Zone Response Type Definitions General Information During programming, you must assign a zone type to each zone, which defines the way in which the system responds to faults in that zone. Zone types are defined below. Zone type 00 is used to program a zone that is not used. Type 00 Zone Not Used Type 01...
Page 15
Zone Response Type Definitions Type 07 Zone type 07 is usually assigned to a zone containing an Emergency button. 24-hour Zone Characteristics: • Sends a report to the central station, and provides alarm sounds externally and at Audible Alarm the keypad. Zone type 08 is usually assigned to a zone containing a button for use in Type 08 personal emergencies or to a zone containing monitoring devices (i.e.: water...
Data Field Descriptions Defaults (where applicable) are Indicated in Text. The following pages list all data fields in this Control (in numerical order). Use the blank programming form to record the data for this installation. Note that both keypad LEDs flash while in Programming mode. The Installer Code is used to enter the 4-digit Master Security Code.
Page 17
Data Field Descriptions The system will wait the time entered before sounding alarm upon Entry Delay 01 * 35 entering if system is not disarmed. UL installations: must be set for a 00-99 = entry delay time in seconds. maximum of 45 seconds The system will wait the time entered before sounding alarm upon Entry Delay 02 * 36...
See choices below See choices below Communication section of this manual. 0 = 3+1; 4+1 ADEMCO Low Speed Standard Note: The maximum number of alarm and alarm restore reports 1 = 3+1; 4+1 Radionics Standard during one armed period is determined by field *93.
Page 19
With ADEMCO Contact ID Reporting: Enter a digit in the first box to enable the zone to report. Use a different digit for each zone until you have used up available digits. If the number of zones exceeds the number of available digits, begin with digit 1 again.
Data Field Descriptions RESTORE REPORT CODES (*70– 76) Sent when the zone that caused an alarm is restored to its non-faulted Alarm Restore Report Code, 1st Digit * 70 condition. 2nd digit is automatically sent as the 2nd digit of the zone (See notes above alarm report code programmed in field *56, if expanded or 4+2 reporting is selected.
Page 21
Data Field Descriptions If long range radio is selected (0), trigger output (terminal screw #8) Long Range Radio/Alarm Audio * 91 will generate a steady signal for burglar alarm (single 3 to 4-second Verification Trigger pulse for all types of silent alarms) or a temporal signal for fire alarm. 0 = long range radio trigger (Refer to Long Range Radio Installation Instructions for appropriate 4 = alarm audio verification...
Page 22
Data Field Descriptions Other Programming Commands * 56 ENHANCED ZONE PROGRAMMING MODE Interactive menu mode used for programming zone attributes and report codes. Refer to the *56 Enhanced Zone Programming Mode section for procedure. * 80 DEVICE PROGRAMMING MENU MODE Interactive menu mode for programming Powerline Carrier Devices.
*56 Enhanced Zone Programming Mode This is an interactive menu mode that is used to program zone numbers, zone types, alarm and report codes, and to identify the type of loop input device. This mode can also be used for entering 5800 Series transmitter serial numbers.
Page 24
*56 Enhanced Zone Programming Mode While in Program mode, press 56 to enter Zone Programming Menu Mode. Refer to the zone assignment table for 56 on the separate programming form. The following explains the *56 prompts in detail. The left two columns identify the prompts and list the available entries for each.
*56 Enhanced Zone Programming Mode Manual Entry - Enter the desired loop number and press [*] to continue (see the transmitter’s Installation Instructions for specific loop designations). Note: The loop number can be changed even if the zone has already been entered. Care should be taken when using this feature as it has the capability to make zones inoperable by creating a mismatch of a working serial number/loop number combination.
Page 26
*56 Enhanced Zone Programming Mode Each zone can have a voice descriptor of up to 3 words that will be Voice descriptor announced whenever the system announces status for that zone. 0 = skip to next zone (A) 1 = enter descriptor mode; existing descriptor for this zone will be announced †...
*80 Device Programming Menu Mode Powerline Carrier devices (eg., X-10 brand devices) are programmable switches that can be used to perform many different functions. They can be used to turn lights on and off, control sounders, or for status indications. In this system, each device must be programmed as to how to act (ACTION), when to activate (START), and when to deactivate (STOP).
Page 28
*80 Device Programming Menu Mode The "STOP" programming determines when and under what conditions the device will be de- STOP activated. The following options are available: Upon Restore of a Zone List Restore Zone List: If a "ZONE LIST" is used as the “Stop” event, the device will de-activate when all the zones in that list restore from a previous fault, trouble, or alarm condition.
Page 29
*80 Device Programming Menu Mode Entering “1” advances to the next prompt below. Powerline Carrier Device programming Entering “0” exits mode, upon which this prompt blinks, indicating the 0 = exit mode mode is inactive. Press [*] + any field number to go to that field. 1 = enter mode Enter device numbers as 2-digit entries.
*81 Zone List Menu Mode While in Program mode, press 81 to enter Zone List Menu Mode. This mode is used to program zone lists for output devices (programmed in 80 menu mode) or Chime-by-Zone in Zone List 3. NOTES: •...
*83 Enhanced Sequential Mode By using this mode, you can add, delete, or change the serial number of a transmitter in a zone, but retain all other existing data that has been programmed for that zone. Note that the *83 Enhanced Sequential mode requires that all zone information must first be entered using the *56 Enhanced Zone Programming mode for all zones below zone number 26 (4 button key area).
Page 32
*83 Enhanced Sequential Mode Notes: 1. A valid template or key has 4 existing Once the serial number has been entered by either selecting a “1” or a zones, each with a zone type, unique loop “2”, you will return to this prompt with the “L” on the display. The serial number.
*84 Assign Zone Voice Descriptors Use this mode to assign voice descriptors for each zone. These are the descriptors that are announced when the system announces any event involving a zone number. Each descriptor can consist of up to 3 words. Press *84 while in Programming mode.
VOICE VOCABULARY INDEX 00 ½ second pause 70 Custom Word #1 14 FIRE 25 MAIN 40 UPSTAIRS 71 Custom Word #2 01 ALARM 15 FLOOR 26 MASTER 41 UTILITY 72 Custom Word #3 02 ATTIC 16 FRONT 27 MESSAGE 73 Custom Word #4 28 MOTION 74 Custom Word #5 42 WINDOW...
General Information The control panel can be remotely programmed from an IBM-compatible Personal Computer (PC), a HAYES Modem, and ADEMCO's Compass Downloader for Windows (as specified below). Downloading may only be performed if a technician is at the site. Multiple security levels protect remote programming against compromise by attempts to defeat the system.
System Operation Security Codes Installer Code The installer programs the 4-digit Installer Code initially as part of the programming procedure. The factory default Installer Code is 4-1-1-2, but may be changed in field The Installer Code is the only code that can enter Programming mode and also, in normal operation mode, is used to enter the Master Code, which allows access to the normal functions of the system.
System Operation Keypad Functions The keypad allows the user to arm and disarm the system, and perform other system functions, such as bypassing zones. Zone and system conditions (alarm, trouble, bypass) are displayed in the display window. When an alarm occurs, keypad sounding and external sounding will occur, and the zone(s) in alarm will be displayed on the keypad.
System Operation Powerline Carrier Devices (e.g. X-10 devices) If Powerline Carrier Devices are used, two keypad entries available to the user are included. They can manually activate or deactivate the device(s) for starting or stopping some action, such as turning lights on or off, etc. These keypad entries are: Security Code* + [#] + [4] + Device # activates (starts) that device.
Testing the System Test Mode After installation is completed, the security system should be carefully tested, as follows. With the system in the disarmed state, check that all zones are intact. If the READY LED is not lit, press the [ ] key to display the faulted zone(s).
This is the “expanded” digit. 4+2 Format Comprises a 4-digit subscriber number and 2-digit report code. ADEMCO Contact ID Comprises a 4-digit subscriber number, 1-digit event qualifier Reporting Format ("new" or "restore"), 3-digit event code, and 3-digit zone number, user number, or system status number (see the following page).
Page 41
SSSS R B b R B R B R B (R B )b ADEMCO Contact ID Reporting takes the following format: CCCC Q EEE GG ZZZ where: CCCC = Customer (subscriber) ID Q = Event qualifier, where: E = new event, and R = restore EEE = Event code (3 hex digits) (for a complete list of event codes, refer to the central office receiver manual) GG = Always “00”...
Troubleshooting Guide S Y S T E M ( i n c l u d i n g W i r e l e s s ) SYMPTOM POSSIBLE CAUSE REMEDY 1a. Transmitter not properly powered. Check or change transmitter's battery. Transmitter signal not received at control.
• Note your ADEMCO customer number and/or company name. Having this information handy will make it easier for us to serve you quickly and effectively. You may contact Technical Support via Toll Free Fax. Please include your return fax number. You will receive a reply within 24 hours.
Regulatory Agency Statements UL NOTICE: This is a "Grade A" residential system. FCC STATEMENT FCC ID: CFS8DLLYNX THIS DEVICE COMPLIES WITH PART 15 OF FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
LYNXR/LYNXR24 PROGRAMMING DEFAULT TABLES (boldface indicates defaults that differ between tables) Function Table 1 Table 2 Table 3 Table 4 Installer code 4112 4112 4112 4112 Quick arm enable Keypad backlight timeout Forced bypass RF house ID code Powerline carrier device house code...
Page 47
*56 ZONE ASSIGNMENT/ALARM REPORT CODES FOR TABLE 1 Zone No. Zone Type Alarm Code Input Type Loop Number Zone Descriptor 3 (RF) 16,12 (FRONT DOOR) 3 (RF) 04,12 (BACK DOOR) 3 (RF) 42 (WINDOW) 3 (RF) 28,10 (MOTION DETECTOR) 5 (BR) 5 (BR) 5 (BR) 5 (BR)
Page 48
LYNX *80 DEFAULT TABLE: APPLIES TO DEFAULT TABLE 4 (devices 2-7 have no default values) Start Stop Zone Type Restore of Zone type Device Number Action Event Zone List System Operation Zone List System operation ** NOTE: If using an X-10 Powerhouse Security SH10A siren as device 8, you must change the device action default to “3” if using default table 4.
Go/No Go Test Mode........11 AC Power Loss ..........8 Contact ID Reporting ....... 41, 45 AC Restore Report Code ......20, 46 Custom Descriptor Number......34 ADEMCO Contact ID Reporting ....18 Custom Descriptors........22 ADEMCO Express ........18, 45 Custom Voice Descriptors......34 Handshake Frequency........40 ADEMCO Low Speed ......18, 45...
Page 50
Local Sounder Disable ........7 Quick Arm ............. 37 Technical Support...........43 Local Sounder Disable Jumper......6 Quick Arm Enable ........16, 46 Temporal Pulse ..........16 Long Range Radio/Alarm Audio Verification Quick Exit............17 Test Mode........37, 39, 42, 43 Trigger............21 Test Report Code..........46 Loop Number ...........
WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons. For example: •...
24 months from the date stamp control on the product or, for products not having an Ademco date stamp, for 12 months from date of original purchase unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply.
INTERFERENCE THAT MAY CAUSE UNDESIRED PLUG-IN OPERATION. RINGER EQUIVALENCE: 0.6B TRANSFORMER 9VAC, 15VA LYNXR IS EQUIPPED WITH AN INTEGRAL RECHARGABLE BATTERY PACK P/N LYNXRCHKIT-SC. REPLACE EVERY FOUR YEARS. LYNXR24 IS EQUIPPED WITH AN INTEGRAL RECHARGABLE BATTERY PACK P/N LYNXRCHKIT-HC. REPLACE EVERY FOUR YEARS.