Instructions for installer: A readily accessible disconnect device shall be incorporated external to the
equipment. Electrician needs to install a single throw double pole switch within a one meter area of the
Lighting Controller. Service to the single throw double pole switch should not be greater than 20 amps. The
warning label must be placed on the switch that says "VIDEOCONFERENCE ROOM LIGHTING
DISCONNECT."
A disconnect device shall have a contact separation of at least 3mm. Vertically mounted disconnect
switches and circuit breakers shall be mounted so that the UP position of the handle is the "on" position.
WARNING: HIGH LEAKAGE CURRENT. EARTH CONNECTION
ESSENTIAL BEFORE CONNECTING SUPPLY.
The main electronics are stationary pluggable equipment Type A with simultaneous multiple connections to
the AC mains supply.
● The building installation must provide a means for connection to protective earth.
● The equipment must be connected to that means.
● A service person must verify that all socket outlets from which the equipment is to be powered
provides a connection to the building protective earth.
To verify, use a suitable long test/wander lead with an ohm meter/multimeter. Connect one end to a
known protective earthing point of the building electrical installation and ensure that there is a reading
of less than one ohm to each earthing contact of all socket outlets to be connected, as shown next.
Socket outlets earthing contact points
If lack of protective earth is discovered at any of the socket outlets, this must first be rectified by
installing a suitable protective earthing conductor in accordance with local wiring code and
regulations. This installation must be carried out by a registered, competent electrician.
Polycom, Inc.
System Rating
21