7-8. Setting Postflow Sequence Display

1
> Poflw
0.0 Sec
Parameter
Select

7-9. Setting Run-in Sequence Display

1
> Runin
ON
100 IPM
Parameter
Select
Poflw
> 0.0 Sec
Set Desired Time
Parameter
Select
Increase/
Decrease
Runin
> ON
100 IPM
Set ON or OFF
Parameter
Select
Increase/
Decrease
> Runin
ON
120 IPM
1
Postflow Parameters Display
Postflow can be adjusted from
0-9.9 seconds. If value set is zero
> Poflw
(0), there is no Postflow sequence.
1.2 Sec
Go to Section 7-9.
Increase
Proceed to next Section.
.
Run-in parameters are not
global
programs; instead, run-in wire
Runin
speed is local at the run-in
ON
program level.
> 120 IPM
1
Run-in Parameters Display
Runin can be turned On or Off.
Set Desired Speed
Runin is a function of wire feed
speed only. This is the speed at
which wire feeds until an arc is
established.
IPM 25-780 (0.6-19.8 mpm).
Increase/
The voltage setting will be the same
Decrease
as Start sequence if time is set in
that sequence; otherwise, this
sequence will use the welding
power source voltage setting.
Parameter
Select
across
multiple
OM-201 396 Page 45