E. Vent Diagrams
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling restops.
• ALWAYS maintain speci ed clearances around venting and restop systems.
Install wall shield and ceiling
Failure to keep insulation or other material away from vent pipe may cause re.
1. Top Vent - Horizontal Termination
Note:
Use SL-D Series
components only.
One Elbow (Natural Gas)
V Minimum
SL-350TRS
90° Elbow
1.5 ft.
152
0.5 ft.
2 ft.
mm
457
1.5 ft.
3 ft.
mm
762
2.5 ft.
5 ft.
mm
3.5 ft.
1.1 m
7 ft.
4.5 ft.
1.4 m
15 ft.
H Maximum= 15 ft. (4.6 m)
V + H Maximum= 40 ft. (12.2 m)
Figure 5.4
Heat & Glo • SL-750TRS-IPI-D, SL-550TRS-IPI-D, SL-350TRS-C • InD • 2065-985 Rev. o • 3/07
14
Venting
H
Maximum
1
SL-550, SL-750TRS-D
457 mm
1 ft.
305 mm
610 mm
2 ft.
610 mm
914 mm
3 ft.
914 mm
1.5 m
5 ft.
1.5 m
2.1 m
7 ft.
2.1 m
4.6 m
15 ft.
4.6 m
WARNING
restops as speci ed.
NOTE: There MUST be a
25% reduction in total H
when using ex vent except
when using the simple up
and out installation (see
Figure 5.3).
One Elbow (Propane)
V Minimum
90° Elbow
0.5 ft.
1.5 ft.
2.5 ft.
3.5 ft.
4.5 ft.
H
1
H
Maximum
1
Not Allowed
305 mm
1 ft.
610 mm
3 ft.
914 mm
5 ft.
1.1 m
7 ft.
1.4 m
15 ft.
H Maximum= 15 ft. (4.6 m)
V + H Maximum = 40 ft. (12.2 m)
V
1
305 mm
914 mm
1.5 m
2.1 m
4.6 m