E. Vent Diagrams
Fire Risk. Explosion Risk.
Do NOT pack insulation or other combustibles between ceiling restops.
• ALWAYS maintain speci ed clearances around venting and restop systems.
•
Install wall shield and ceiling
Failure to keep insulation or other material away from vent pipe may cause re.
1. Top Vent - Horizontal Termination
Note:
Use SL-D Series
components only.
One Elbow (Natural Gas)
V Minimum
SL-350TRS
90° Elbow
1.5 ft.
152
0.5 ft.
2 ft.
mm
457
1.5 ft.
3 ft.
mm
762
2.5 ft.
5 ft.
mm
3.5 ft.
1.1 m
7 ft.
4.5 ft.
1.4 m
15 ft.
H Maximum= 15 ft. (4.6 m)
V + H Maximum= 40 ft. (12.2 m)
Figure 5.4
Heat & Glo • SL-750TRS-IPI-D, SL-550TRS-IPI-D, SL-350TRS-C • InD • 2065-985 Rev. o • 3/07
14
Venting
H
Maximum
1
SL-550, SL-750TRS-D
457 mm
1 ft.
305 mm
610 mm
2 ft.
610 mm
914 mm
3 ft.
914 mm
1.5 m
5 ft.
1.5 m
2.1 m
7 ft.
2.1 m
4.6 m
15 ft.
4.6 m
WARNING
restops as speci ed.
NOTE: There MUST be a
25% reduction in total H
when using ex vent except
when using the simple up
and out installation (see
Figure 5.3).
One Elbow (Propane)
V Minimum
90° Elbow
0.5 ft.
1.5 ft.
2.5 ft.
3.5 ft.
4.5 ft.
H
1
H
Maximum
1
Not Allowed
305 mm
1 ft.
610 mm
3 ft.
914 mm
5 ft.
1.1 m
7 ft.
1.4 m
15 ft.
H Maximum= 15 ft. (4.6 m)
V + H Maximum = 40 ft. (12.2 m)
V
1
305 mm
914 mm
1.5 m
2.1 m
4.6 m