No.
Name and Description
03
Clear DF1 Counts
No action if set to "Ready." Resets the
DF1 statistical parameter DF1 Packets
Sent (04) and DF1 Packets Rcvd (05) to
0 if set to "Clear Counts." This parameter
is a command. It will be reset to "0 =
Ready" after a "Clear Counts" command
has been performed.
04
DF1 Packets Sent
Displays the number of DF1 packets sent
by the converter. The value of this
parameter is normally approximately
equal to the value of DF1 Packets Rcvd
(05).
05
DF1 Packets Rcvd
Displays the number of DF1 packets
received by the converter. The value of
this parameter is normally approximately
equal to the value of DF1 Packets Sent
(04).
06
Interface Mode
Sets the interface operating mode:
Auto: The converter will automatically run
DPI if connected to a DPI drive.
Set this parameter to "Auto" (default).
07
DPI Data Rate
Displays the data rate used by the DPI
host drive. This data rate is set in the
drive, and the converter autobauds to it.
08
Ref/Fdbk Size
Displays the size of the
Reference/Feedback. The host drive
determines the size of the
Reference/Feedback. The converter
automatically uses the correct size.
09
Datalink Size
Displays the size of each Datalink word.
The host drive determines the size of
Datalinks.
Details
Default:
0 = Ready
Values:
0 = Ready
1 = Clear Counts
Type:
Read/Write
Reset Required:No
Default: 0
Minimum:0
Maximum:4294967295
Type:Read Only
Default: 0
Minimum:0
Maximum:4294967295
Type:Read Only
Default:
0 = Auto
Values:
0 = Auto
1 = SCANport
Type:
Read/Write
Reset Required:Yes
Default:
0
Values:
0 = 125 kbps
1 = 500 kbps
Type:
Read Only
Default:
0 = 16-bit
Value:
0 = 16-bit
1 = 32-bit
Type:
Read Only
Default:
0 = 16-bit
Values:
0 = 16-bit
1 = 32-bit
Type:
Read Only