Servicing schedule
4.6
CLEANING THE CONDENSATE DRAIN
SIPHON
In order to check and clean the siphon carry out the following
steps:
-
disconnect the transparent pipe (A) check that no deposits
have accumulated inside the siphon. If there are any de-
posits flush them out with clean water;
-
reassemble the siphon in reverse order.
Danger!
Before commissioning the appliance fill the
siphon via the filling hole and check the
correct drainage of the condensate.
If the appliance is used with the condensate
drain siphon empty this could lead to danger
of intoxication following the escape of flue
gasses.
4.7
SEALING GASKET BETWEEN
DISTRIBUTOR AND BOILER BODY
DANGER!
It is absolutely necessary to replace the
gasket at any time the inspection or mainte-
nance is made on the burner.
When refitting the mixer tighten the nuts
progressively and in crossed way, by using a
dynamometric wrench adjusted at 10 Nm (1
kgm).
44
Condensate
coming from
the boiler
Condensate
drain.
Pipe to be
connected
to the sewage
A
Mixer
Gasket
between
mixer and
boiler body.
Burner
Body