Testing Ignition Safety Shut Off Device - Lattner Boiler Company Alkon 90 Installation And Servicing Manual

Alkon 90 condensing gas boiler
Table of Contents

Advertisement

Instructions for the installer
3.25 -
TESTING THE IGNITION SAFETY
SHUT OFF DEVICE
-
Power on by switching ON-OFF switch
-
Check that the boiler is connected to the electrical
supply; the green indicator led "Q" (
panel must be illuminated.
-
Create a request in CH by pressing key indicate.
-
Turn the gas valve knob, in OFF position.
-
After 1sec, boiler switch off,
Lock-out indicator
led illuminated
+ fault indicator led
-
Press Reset Key will displayed the fault code LF (loss
of flame), the boiler will retry ignition cycle (7 seconds)
after which if was not removed the cause of the fault
(gas tap) the boiler will shut off.
36
) on the control
LIGHT
BLUE