Technical features and dimensions

TECHNICAL FEATURES

2
AND DIMENSIONS
2.1 -
TECHNICAL FEATURES
The ALKON 90 boiler is a low water content thermal element
about 2,64 gal (10 l), with a built-in premix gas burner, for
heating only.
It is mainly used as element for the modular boilers in casca-
de (max 4 boilers).
PECULIAR CHARACTERISTICS:
1)
modular structure to tall integration.
2)
mainly for outdoor installation
3)
prearranged for quick installation '' Plug and Play '' also
in cascade of up to 4 modules.
4)
modulation ratio of the single module
5)
control for every single module, with display and
diagnostic
These boilers have an input head power of:
341,000 Btu (99,94 kW), These boilers are designed for use
on gas category IV.
The ALKON boiler is supplied complete with all the safety
and control devices in accordance with all the current
regulations and its technical and functional features comply
with the regulations prescribed by:
ANSI Z21.13 / CSA 4.9 - Gas-fired low pressure
steam and hot water boilers
DESCRIPTION OF COMPONENTS AND FEATURES
Aluminium heat exchanger/condenser;
Premixed combustion group working at constant air-gas
ratio
Electronic ignition;
Safety limit thermostat;
8
Safety high limit thermostat;
Flow temperature sensor;
Return temperature sensor;
Automatic air vent;
Control panel with electrical protection
Flame modulation in function of the absorbed power;
Pump overrun function;
Pump
eBUS connection
E8 regulator (optional)
BCM (optional)
ON/OFF switch
Temperature adjustment in heating mode between
86 ÷176 °F (30 and 80°C)
• Smoke pressure switch
OPTIONAL KITS:
• Kit of manifold for additional safety devices
• Krömschröder controller E8/Expansion modules and
modulating thermostats
• Mixing bottle Kit
• Chimney for single, battery or cascade mounting
• Kit of blind flanges and hydraulic manifolds.
Warning
for Outdoor installation is necessary
Electrical resistor kit for condensate
siphon
Electrical resistor kit on Flow and Return
manifolds
Kit esternal top.