Boiler Location In A Boiler House - Lattner Boiler Company Alkon 90 Installation And Servicing Manual

Alkon 90 condensing gas boiler
Table of Contents

Advertisement

Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appliance.
Never use or store any chlorinated detergents or haloge-
nated hydrocarbons (e.g. in spraycans, solvents and de-
tergents, paints, adhesives) in proximity of the boiler.
The boiler must be installed in such a way that it is pro-
tected from water (dripping, spraying, rain, etc.) during
operation and service (circulator replacement, condensa-
te trap, control replacement, etc.)
This boiler is intended for indoor installation only
For outdoor installation see Warning for Outdoor instal-
lation at page 8.
Products to avoid present in boiler room
and/or around combustion air intake
Spray cans containing chloro-/fluorcarbons
Ammonium and/or ammonium solutions
Permanent wave solutions
Chlorinated waxes and/or cleaners
Swimming pool chemicals based on chlorine
Calcium chloride used for thawing
Sodium chloride used for water softening
Refrigerant leaks
Paint or varnish removers
Hydrochloric acid/muriatic acid
Cements and glues
Antistatic fabric softeners used in clothes dryers
Chlorine-type bleaches, detergents, and cleaning solvents
found in household laundry rooms
Adhesives used to fasten building products and
other similar products
Areas likely to have contaminants
Dry cleaning/laundry areas and establishments
Swimming pools
Metal fabrication plants
Beauty shops
Refrigeration repair shops
Photo processing plants
Auto body shops
Plastic manufacturing plants
Furniture refinishing areas and establishments
New building construction
Remodeling areas
Garages with workshops
Instructions for the installer